| | SIMATIC DP, 5 ELECTRON. MODULES ET 200S: 4DI UC 24V...48V, 15 MM WIDTH, WITH LED SF (GROUP FAULT), 5 PIECES PER PACKAGING UNIT |
| |
| Supply voltage |
| 24 V DC | Yes; From power module |
| permissible range, lower limit (DC) | 24 V |
| permissible range, upper limit (DC) | 48 V |
| 24 V AC | Yes |
| permissible range, lower limit (AC) | 24 V |
| permissible range, upper limit (AC) | 48 V |
| Reverse polarity protection | Yes; AC or DC automatic |
| Input current |
| from backplane bus 3.3 V DC, max. | 10 mA |
| from supply voltage L+, max. | Dependent on encoder |
| Encoder supply |
| Output voltage | min. L+ (-0.5 V), under load |
| Output current, rated value | 500 mA |
| Output current, permissible range | 0 to 500 mA |
| Output current |
| Short-circuit protection | Yes; per module |
| Power losses |
| Power loss, typ. | 0.7 W |
| Address area |
| Address space per module |
| with packing | 4 bit |
| without packing | 1 byte |
| Digital inputs |
| Number/binary inputs | 4 |
| Input characteristic curve acc. to IEC 61131, Type 1 | Yes |
| Input voltage |
| Type of input voltage | AC/DC |
| Rated value, UC | 24 V; 24 to 48 V UC |
| for signal "0" | -6 to 6 V DC, 0 to 5 V AC |
| for signal "1" | -15 to -57.6 V DC; -15 to 57.6 V DC; 15 to 48 V AC |
| Frequency range | 47 to 63 Hz |
| Input current |
| for signal "1", typ. | 10 mA; 4 to 10 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| at "0" to "1", max. | 15 ms |
| at "1" to "0", max. | 15 ms |
| Encoder connection |
| Fixed current limitation for wire break monitoring, min. | 18 kΩ; Rated voltage 24 V (15 V to 35 V); rated voltage 48 V (30 V to 60 V): 39 kohms |
| Cable length |
| Cable length, shielded, max. | 1000 m |
| Cable length unshielded, max. | 600 m |
| Encoder |
| Connectable encoders |
| 2-wire sensor | Yes |
| Permissible quiescent current (2-wire sensor), max. | 2 mA; (0.5 to 2 mA), a minimum load current is necessary for wire break diagnostics. |
| Isochronous mode |
| Isochronous operation (application synchronized up to terminal) | Yes |
| Interrupts/diagnostics/status information |
| Diagnostic messages |
| Diagnostic functions | Yes; Parameterizable |
| Diagnostics indication LED |
| Group error SF (red) | Yes |
| Status indicator digital input (green) | Yes; per channel |
| Galvanic isolation |
| Galvanic isolation digital inputs |
| between the channels | No |
| between the channels and the backplane bus | Yes |
| Permissible potential difference |
| between different circuits | 75 VDC / 60 VAC |
| Isolation |
| Isolation checked with | 2500 V DC |
| Dimensions |
| Width | 15 mm |
| Height | 81 mm |
| Depth | 52 mm |
| Weight |
| Weight, approx. | 35 g |
| Status | Mar 12, 2012 |