| | SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 2 DI STANDARD 24V DC, 15 MM WIDTH, 5 PIECES PER PACKAGING UNIT |
| |
| Supply voltage |
| 24 V DC | Yes; From power module |
| Reverse polarity protection | Yes |
| Input current |
| from backplane bus 3.3 V DC, max. | 10 mA |
| from supply voltage L+, max. | Dependent on encoder |
| Encoder supply |
| Output voltage | min. L+ (-0.5 V), under load |
| Output current, rated value | 500 mA |
| Output current, permissible range | 0 to 500 mA |
| Power losses |
| Power loss, typ. | 0.4 W |
| Address area |
| Address space per module |
| with packing | 2 bit |
| without packing | 1 byte |
| Digital inputs |
| Number/binary inputs | 2 |
| Input characteristic curve acc. to IEC 61131, Type 1 | Yes |
| Input voltage |
| Rated value, DC | 24 V |
| for signal "0" | -30 to +5 V |
| for signal "1" | 15 to 30 V |
| Input current |
| for signal "1", typ. | 7 mA; at 24 V |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| Parameterizable | No |
| at "0" to "1", min. | 2 ms; typically 3 ms |
| at "0" to "1", max. | 4.5 ms |
| at "1" to "0", min. | 2 ms; typically 3 ms |
| at "1" to "0", max. | 4.5 ms |
| Cable length |
| Cable length, shielded, max. | 1000 m |
| Cable length unshielded, max. | 600 m |
| Encoder |
| Connectable encoders |
| 2-wire sensor | Yes |
| Permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Interrupts/diagnostics/status information |
| Diagnostic messages |
| Diagnostic functions | No |
| Diagnostics indication LED |
| Status indicator digital input (green) | Yes |
| Galvanic isolation |
| Galvanic isolation digital inputs |
| between the channels | No |
| between the channels and the backplane bus | Yes |
| Permissible potential difference |
| between different circuits | 75 VDC / 60 VAC |
| Isolation |
| Isolation checked with | 500 V DC |
| Dimensions |
| Width | 15 mm |
| Height | 81 mm |
| Depth | 52 mm |
| Weight |
| Weight, approx. | 35 g |
| Status | Mar 12, 2012 |