| | SIMATIC DP, ELECTRONIC MODULES FOR ET200PRO 4 DIO / 4 DO DC 24V, 0.5A MODULE DIAGNOSTICS; INCLUSIVE BUS MODULE, CONNECTING MODULE IO 6ES7194-4CB50-0AA0 MUST BE ORDERED SEPERATELY |
| |
| Supply voltage |
| 24 V DC | Yes |
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes; Against destruction; encoder power supply outputs applied with reversed polarity |
| Load voltage 2L+ |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes; against destruction; load increasing |
| Input current |
| from load voltage 1L+ (unswitched voltage) | 20 mA |
| from load voltage 2L+, max. | 20 mA |
| Encoder supply |
| Number of outputs | 4 |
| Output current, rated value | 1 A; per module, electronic |
| 24 V encoder supply |
| Short-circuit protection | Yes; per module, electronic |
| Power losses |
| Power loss, typ. | 3 W |
| Digital inputs |
| Number/binary inputs | 4; 4 DIOs can be parameterized |
| Input characteristic curve acc. to IEC 61131, Type 3 | Yes |
| Number of simultaneously controllable inputs |
| all mounting positions |
| up to 60 °C, max. | 4; Up to 55 °C |
| Input voltage |
| Rated value, DC | 24 V |
| for signal "0" | -3 to +5 V |
| for signal "1" | 11 to 30 V |
| Input current |
| for signal "0", max. (permissible quiescent current) | 1.5 mA |
| for signal "1", typ. | 7 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| at "0" to "1", max. | 4.8 ms |
| at "1" to "0", max. | 4.8 ms |
| Cable length |
| Cable length unshielded, max. | 30 m |
| Digital outputs |
| Number/binary outputs | 8; 4 DO fixed, 4 DIO parameterizable |
| In groups of | 2; 2 load groups for 4 outputs each |
| Functionality/short-circuit strength | Yes; per channel, electronic |
| Response threshold, typ. | 0.7 A |
| Limitation of inductive shutdown voltage to | Typ. (L1+, L2+) -47 V |
| Switching capacity of the outputs |
| on lamp load, max. | 5 W |
| Controlling a digital input | Yes |
| Output current |
| for signal "1" rated value | 0.5 A |
| for signal "0" residual current, max. | 0.5 mA |
| Parallel switching of 2 outputs |
| for increased power | No |
| for redundant control of a load | Yes |
| Switching frequency |
| with resistive load, max. | 100 Hz |
| with inductive load, max. | 0.5 Hz |
| on lamp load, max. | 1 Hz |
| Aggregate current of outputs (per group) |
| all mounting positions |
| up to 55 °C, max. | 2 A |
| Cable length |
| Cable length unshielded, max. | 30 m |
| Interrupts/diagnostics/status information |
| Status indicator | Yes; Green LED |
| Alarms |
| Diagnostic alarm | Yes |
| Diagnostic messages |
| Diagnostic functions | Yes |
| Diagnostic information readable | Yes |
| Short circuit | Yes; Short-circuit of outputs to ground; module by module |
| Short circuit encoder supply | Yes; per module |
| Group error | Yes |
| Galvanic isolation |
| between the load voltages | Yes |
| between load voltage and all other switching components | Yes |
| Galvanic isolation digital inputs |
| between the channels | No |
| Permissible potential difference |
| between different circuits | 75 VDC / 60 VAC |
| Isolation |
| tested with |
| 24 V DC circuits | 500 V |
| Dimensions |
| Width | 45 mm |
| Height | 130 mm |
| Depth | 35 mm |
| Weight |
| Weight | 140 g |
| Status | Mar 12, 2012 |