6EP1437-2BA00 - SITOP POWER 30 STABILIZED POWER SUPPLY INPUT: 400-500 V 3 AC OUTPUT: 24 V DC/30 A (siemens) - Quad Industry GmbH

Артикул: 6EP1437-2BA00
Наименование: SITOP POWER 30 STABILIZED POWER SUPPLY INPUT: 400-500 V 3 AC OUTPUT: 24 V DC/30 A (siemens)
Производитель: Siemens


SITOP POWER 30 STABILIZED POWER SUPPLY INPUT: 400-500 V 3 AC OUTPUT: 24 V DC/30 A
Technical specifications
Product SITOP power
Power supply, type 24 V/30 A
Input
Input 3-phase AC
Rated voltage value Vin rated 400 500 V
Voltage range 360 550 V
  • Note
340 ... 360 V for max. 2 s or at max. 0.9 x Iout rated
Wide-range input Yes
Overvoltage resistance 2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min. 4.5 ms
Mains buffering at Vin = 360 V
Rated line frequency 50/ 60 Hz
Rated line range 47... 63 Hz
Input current / at nominal level of the input voltage 400 V 1.4 A
Switch-on current limiting (+25 °C), max. 25 A
Inrush current A²s 1 A²·s
Built-in incoming fuse none
Protection in the mains power input (IEC 898) Required: 3-pole connected miniature circuit breaker characteristic C up to 25 A (recommended: 6 A) or circuit-breaker 3RV1021-1DA10 (setting 3 A) or 3RV1721-1DD10 (UL 489)
Output
Output controlled, isolated DC voltage
Rated voltage 24 V
Total tolerance, static ± 3 %
Residual ripple peak-peak, max. 150 mV
Residual ripple peak-peak, typ. 50 mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 240 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 200 mV
Adjustment range 22.8 26.4 V
Product feature / output voltage adjustable Yes
Output voltage setting via potentiometer
  • Note
only permissible at ambient temperatur 0 °C to +45 °C
Status display Green LED for 24 V OK
On/off behavior Slight overshoot of Vout (< 2 V for max. 500 ms)
Startup delay, max. 3 s
Voltage rise, typ. 40 ms
Rated current value Iout rated 30 A
Current range 0 30 A
delivered active power / typ. 720 W
short-term overload current / at short-circuit during run-up / typical 60 A
Duration of overloading ability for excess current / on short-circuiting during the start-up 600 ms
short-term overload current / at short-circuit during operation / typical 60 A
Duration of overloading ability for excess current / on short-circuiting during the operational phase 600 ms
Parallel switching for enhanced performance Yes
  • Note
only permissable at ambient temperature 0 °C to 45 °C
Numbers of parallel switchable units for enhanced performance 2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 90 %
Power loss at Vout rated, Iout rated, approx. 80 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max. 1 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. 4 %
Setting time / maximum 3 ms
Protection and monitoring
Output overvoltage protection Yes, according to EN 60950
Current limitation 31.5 39 A
Characteristic feature of the output / short-circuit protected Yes
Short-circuit protection Electronic shutdown, automatic restart
Enduring short circuit current / Effective level / maximum 48 A
Overload/short-circuit indicator -
Safety
Primary/secondary isolation Yes
Potential separation Safety extra low output voltage Vout according to EN 60950-1
Protection class Class I
stray current / maximum 3.5 mA
stray current / typical 0.78 mA
CE mark Yes
UL/CSA approval Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289
Explosion protection -
FM approval -
CB approval Yes
Marine approval -
Degree of protection (EN 60529) IP20
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation EN 61000-3-2
Noise immunity EN 61000-6-2
Operating data

Назад в раздел