| | SINVERT PVS COMBINERBOX 108, ARRAY JUNCTION BOX FOR PV, 8 DC INPUTS, IP54, IEC, WITH FUSE HOLDER, OVERLOAD PROTECTION |
| |
| General technical data: |
| product brand name | | SINVERT |
| Product-type designation | | SINVERT PVS Combiner Box 108 |
| product designation | | Terminal box |
| Type of installation | | indoor installation / outdoor installation |
| Protection class IP | | IP54 |
| Operating resource protection class | | II (protective insulation) |
| Degree of pollution | | 3 |
| Installation altitude / at a height over sea level / maximum | m | 2,000 |
| Ambient temperature | | |
| | °C | -20… +45 |
| | °C | -20… +45 |
| | °C | -20… +45 |
| Relative humidity / without condensation | | |
| | % | 0… 50 |
| RAL color number | | RAL 7035 |
| Case | | |
| | | Polyester |
| | | Polyester |
| Product characteristic / resistant to UV radiation | | Yes |
| Fire classification / non-flammable | | Yes |
| Product function / current measurement | | No |
| Product component / pressure compensation element | | Yes |
| Number of pressure compensation elements | | 1 |
| Type of compensation element | | Diaphragm |
| Product function / Overvoltage protection | | Yes |
| Design of the overload protection | | Type 2 |
| |
| Inputs: | | |
| Input voltage / maximum | V | 1,000 |
| Number of inputs | | 8 |
| Input current / per input / maximum | A | 10 |
| Product component / at input / protection | | Yes |
| Type of protection / at input | | Cylinder fuse link |
| Number of inputs / per protection | | 1 |
| |
| Outputs: | | |
| Output current / maximum | A | 104 |
| Product component / at output / protection | | No |
| Product component / at output / disconnecting device | | No |
| |
| Connections: | | |
| Design of the electrical connection / at the DC input | | Cage clamp terminal |
| Tightening torque | | |
| | N·m | 2… 2.5 |
| Connectable conductor cross-section / at DC input | | |
| | mm² | 0.75… 25 |
| | mm² | 0.75… 25 |
| | | |
- with conductor end processing
| mm² | 1.5… 25 |
| | | |
- with conductor end processing
| mm² | 1.5… 25 |
| Outside diameter / of cable sheath / for cable gland / at DC input | | |
| | mm | 4.5… 10 |
| Type of electrical terminal / at DC output | | Stud terminal |
| Type of thread / for terminal screw / at DC output | | M8 |
| Tightening torque | | |
| | N·m | 6… 12 |
| Connectable conductor cross-section / at DC output | | |
| | | |
- with conductor end processing
| mm² | 2.5… 95 |
| | | |
- with conductor end processing
| mm² | 2.5… 95 |
| Outside diameter / of cable sheath / for cable gland / at DC output | | |
| | mm | 15… 21 |
| Design of the electrical connection / for grounding | | Cage clamp terminal |
| Tightening torque | | |
| | N·m | 1.2… 2.4 |
| Connectable conductor cross-section / for grounding | | |
| | mm² | 1.5… 16 |
| | mm² | 1.5… 25 |
| | | |
- with conductor end processing
| mm² | 1.5… 16 |
| | | |
- with conductor end processing
| mm² | 1.5… 16 |
| Outside diameter / of cable sheath / for cable gland / for grounding | | |
| | mm | 4.5… 10 |
| |
| Installation/mounting/dimensions: |
| Built in orientation | | Vertical |
| Type of mounting | | wall mounting |
| Cable gland version | | from below |
| Width | mm | 600 |
| Depth | mm | 132 |
| Height | mm | 400 |
| Weight | kg | 10.5 |
| |
|
|