| | SINVERT PVS600 INVERTER FOR PV, GRID CONNECT. MV TRANS, IEC 60HZ, 3P, STANDARD MPP, UMAX 820VDC, 3 DC-INPUTS, IP20, AIR COOLING, PV FIELD GROUNDING NEG. POLE, CABINET HEATING |
| |
| General technical data: |
| product brand name | | SINVERT |
| Product-type designation | | SINVERT PVS600 |
| product designation | | photovoltaic inverter |
| Output class for PV inverters | | 600 |
| Efficiency / maximum possible | % | 98.7 |
| Efficiency | | |
| | | 98.4 |
| | | 98.6 |
| Design of PV inverter unit | | single device |
| Number of PV inverter sub-units | | 1 |
| Type of installation | | indoor installation |
| Protection class IP | | IP20 |
| Operating resource protection class | | I |
| Design of the interface / for communication | | Ethernet |
| A-rated sound power level / maximum | dB | 80 |
| Design of the display | | LCD-TFT |
| National language / at the indicator of the display / selectable | | English, German |
| Connection method for PV inverters | | without transformer |
| |
| Output (AC side): | | |
| Phase number | | 3 |
| Output voltage / on the AC side / for infeed operation / nominal value | V | 370 |
| Output voltage / on the AC side | | |
| | V | 314.5… 407 |
| Power factor / at nominal value of active power supplied / nominal value | | 1 |
| Active power supplied / on the AC side | | |
- in permanent operation / nominal value
| W | 600,000 |
| | W | 600,000 |
| Current supplied / on the AC side / maximum | A | 936 |
| Line frequency / suitable for infeed operation / nominal value | Hz | 60 |
| Line frequency | | |
- suitable for infeed operation
| Hz | 58.8… 61.2 |
| Power factor inductive | | 0.95 |
| Power factor capacitive | | 0.95 |
| Relative residual ripple / of AC current / at nominal value of the AC active power / on unloaded line / maximum | % | 2 |
| Grounding concept / on the AC side | | IT |
| Design of the overvoltage protection / on the AC side | | type 1/2 |
| |
| Input (DC side): | | |
| MPP voltage | V | 570… 750 |
| Consumed active power / on the DC side / nominal value | W | 613,000 |
| Input voltage / on the DC side | | |
- for the start of the infeed operation
| V | 700 |
- for possible infeed operation
| V | 570… 750 |
| | V | 650 |
| | V | 820 |
| Number of inputs / on the DC side | | 3 |
| Input current / per DC input / maximum | A | 368 |
| Total power used / on the DC side / maximum | A | 1,104 |
| Overcurrent strength / per DC input / nominal value | A | 368 |
| Design of the overvoltage protection / on the DC side | | type 2 |
| |
| External auxiliary voltage supply: | | |
| Auxiliary voltage / nominal value | V | 400 |
| Active power consumed / from external auxiliary voltage | | |
| | | |
- with cabinet heating / maximum
| W | 3,750 |
| Grounding concept / for auxiliary power supply external | | TN-S |
| Auxiliary voltage frequency / nominal value | Hz | 60 |
| |
| Ambient conditions: | | |
| Installation altitude | m | 0… 2,000 |
| | m | 0… 1,000 |
| Incoming air temperature / at nominal value of active power supplied / maximum | °C | 40 |
| Ambient temperature | | |
| | °C | 0… 50 |
| | °C | -25… +70 |
| | °C | -25… +70 |
| Relative humidity / without condensation | | |
| | % | 0… 95 |
| Relative humidity | | |
| | % | 95 |
| | % | 95 |
| Climatic class | | 3K3 |
| Type of cooling | | forced-air cooling via fan |
| Cooling air flow | m³/h | 6,500 |
| Nature of the ventilation | | air intake cabinet front/air outlet cabinet top |
| |
| Mechanical data: | | |
| Built in orientation | | vertical |
| Width / of PV inverter subunits | mm | 2,700 |
| Height / of PV inverter subunits | mm | 2,100 |
| Depth / of PV inverter subunits | mm | 730 |
| Weight / of the single device | kg | 2,090 |
| Type of mounting | | Floor mounting installation |
| |
| Certificates/approvals: |
| Verification of suitability / CE mark | | Yes |
| Product quality | | |
| | | |
| | | Yes |
| | | |