| | SIPLUS ET200S EM 2AI TC HF 0 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7134-4NB01-0AB0 . 15 MM WIDE, 15 BIT + SIGN WITH INTERNAL TEMERATURE COMPENSATION |
| |
| Supply voltage |
| Load voltage L+ |
| Rated value (DC) | 24 V; From power module |
| Reverse polarity protection | Yes |
| Input current |
| from load voltage L+ (without load), max. | 30 mA |
| from backplane bus 3.3 V DC, max. | 10 mA |
| Power losses |
| Power loss, typ. | 0.6 W |
| Address area |
| Address space per module |
| Address space per module, max. | 4 byte |
| Analog inputs |
| Number of analog inputs | 2 |
| permissible input voltage for voltage input (destruction limit), max. | 20 V; +/-20 V, continuous |
| Cycle time (all channels) max. | Number of active channels per module x basic conversion time |
| Technical unit for temperature measurement adjustable | Yes |
| Input ranges |
| Voltage | Yes |
| Current | No |
| Thermocouple | Yes |
| Resistance thermometer | No |
| Resistance | No |
| Input ranges (rated values), voltages |
| -80 mV to +80 mV | Yes |
| Input resistance (-80 mV to +80 mV) | 1 MΩ |
| Input ranges (rated values), thermoelements |
| Type B | Yes |
| Input resistance (Type B) | 1 MΩ |
| Type C | Yes |
| Input resistance (Type C) | 1 MΩ |
| Type E | Yes |
| Input resistance (Type E) | 1 MΩ |
| Type J | Yes |
| Input resistance (type J) | 1 MΩ |
| Type K | Yes |
| Input resistance (Type K) | 1 MΩ |
| Type L | Yes |
| Input resistance (Type L) | 1 MΩ |
| Type N | Yes |
| Input resistance (Type N) | 1 MΩ |
| Type R | Yes |
| Input resistance (Type R) | 1 MΩ |
| Type S | Yes |
| Input resistance (Type S) | 1 MΩ |
| Type T | Yes |
| Input resistance (Type T) | 1 MΩ |
| Thermocouple (TC) |
| for thermocouples | Type B, C, E, J, K, L, N, R, S, T to IEC 584 |
| Temperature compensation |
| internal temperature compensation | Yes; possible with TM-E15S24-AT, TM-E15C24-AT |
| external temperature compensation with compensations socket | Yes; one external compensating box per channel |
| Characteristic linearization |
| Parameterizable | Yes |
| Cable length |
| Cable length, shielded, max. | 50 m |
| Analog value creation |
| Measurement principle | integrating |
| Integrations and conversion time/ resolution per channel |
| Resolution with overrange (bit including sign), max. | 16 bit |
| Integration time, ms | 16.7 / 20 ms |
| Interference voltage suppression for interference frequency f1 in Hz | 60 / 50 Hz |
| Conversion time (per channel) | 66 ms; 66 / 80 ms; additional conversion time for diagnostic wire break test |
| Smoothing of measured values |
| Parameterizable | Yes; In four stages by means of digital filtering |
| Step: None | Yes; 1 x cycle time |
| Step: low | Yes; 4 x cycle time |
| Step: Medium | Yes; 32 x cycle time |
| Step: High | Yes; 64 x cycle time |
| Errors/accuracies |
| Linearity error (relative to input area) | +/- 0,01 % |
| Temperature error (relative to input area) | +/- 0,005 %/K |
| Crosstalk between the inputs, min. | -50 dB |
| Repeat accuracy in settled status at 25 °C (relative to input area) | +/- 0,05 % |
| Operational limit in overall temperature range |
| Voltage, relative to input area | +/- 0,1 %; +/-1.5 K for thermocouples, +/-7 K for thermocouples type C,+/-2.5 K with static thermal state (ambient temperature change < 0.3 K/min) |
| Basic error limit (operational limit at 25 °C) |
| Voltage, relative to input area | +/- 0,05 %; +/-1 K with thermocouples, +/-5 K with thermocouples type C, +/-1.5 K with static thermal state (ambient temperature change < 0.3 K/min) |
| Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency |
| Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
| common mode voltage (USS < 2.5 V) , min. | 90 dB |
| Interrupts/diagnostics/status information |
| Diagnostic messages |
| Wire break | Yes; only thermocouples |
| Group error | Yes |
| Overflow/underflow | Yes |
| Diagnostics indication LED |
| Group error SF (red) | Yes |
| Parameter |
| Diagnosis: wire break | Disable / enable (wire break is detected only in thermocouples) |
| Measurement type/range | Deactivated/ +/- 80 mV/ TC-EL Type T (Cu-CuNi)/ TC-EL Type K (NiCr-Ni)/ TC-EL Type B (PtRh-PtRh)/ TC-EL Type c (Wer-Wer) TC-EL Type N (NiCrSi-NiSi)/ TC-EL Type E (NiCr-CuNi)/ TC-EL Type R (PtRh-Pt)/ TC-EL Type S (PtRh-Pt)/ TC-EL Type J (Fe-Cu-Ni)/ TC |
| Group diagnostics | Disable / enable |
| Overflow/underflow | Disable / enable |
| Comparison point | none / yes, internal |
| Unit | Celsius / Fahrenheit |
| Galvanic isolation |
| Galvanic isolation analog inputs |
| between the channels | No |
| between the channels and the backplane bus | Yes |
| between the channels and the load voltage L+ | Yes |
| Permissible potential difference |
| between inputs and MANA (UCM) | 140 V DC/100 V AC |
| between MANA and M internally (UISO) | 75 VDC / 60 VAC |
| Isolation |
| Isolation checked with | 500 V DC |
| Standards, approvals, certificates |
| CE mark | Yes |
| Ambient conditions |
| Extended ambient conditions |
Relative to ambient temperature-atmospheric
|