| | SIPLUS ET200S EM 2AI STANDARD I -25 ... +60 DEGREES C BASED ON 6ES7134-4GB01-0AB0 |
| |
| Supply voltage |
| Load voltage L+ |
| Rated value (DC) | 24 V; From power module |
| Reverse polarity protection | Yes; Destruction limit 35 mA per channel |
| Input current |
| from load voltage L+ (without load), max. | 80 mA |
| from backplane bus 3.3 V DC, max. | 10 mA |
| Power losses |
| Power loss, typ. | 0.6 W |
| Address area |
| Address space per module |
| Address space per module, max. | 4 byte |
| Analog inputs |
| Number of analog inputs | 2 |
| Cycle time (all channels) max. | Number of active channels per module x basic conversion time |
| permissible input current for current input (destruction limit), max. | 40 mA |
| Input ranges |
| Voltage | No |
| Current | Yes |
| Thermocouple | No |
| Resistance thermometer | No |
| Resistance | No |
| Input ranges (rated values), currents |
| 4 to 20 mA | Yes; on 50 ohms |
| Cable length |
| Cable length, shielded, max. | 200 m |
| Analog value creation |
| Measurement principle | integrating |
| Integrations and conversion time/ resolution per channel |
| Resolution with overrange (bit including sign), max. | 13 bit; 4 to 20 mA: 13 bits |
| Integration time, ms | 16.7 / 20 ms |
| Interference voltage suppression for interference frequency f1 in Hz | 60 / 50 Hz |
| Conversion time (per channel) | 65 ms; 55 / 65 ms |
| Smoothing of measured values |
| Parameterizable | Yes; In four stages by means of digital filtering |
| Step: None | Yes; 1 x cycle time |
| Step: low | Yes; 4 x cycle time |
| Step: Medium | Yes; 32 x cycle time |
| Step: High | Yes; 64 x cycle time |
| Encoder |
| Connection of signal encoders |
| Burden of 2-wire transmitter, max. | 750 Ω |
| Errors/accuracies |
| Linearity error (relative to input area) | +/- 0,01 % |
| Temperature error (relative to input area) | +/- 0,005 %/K |
| Crosstalk between the inputs, min. | -50 dB |
| Repeat accuracy in settled status at 25 °C (relative to input area) | +/- 0,05 % |
| Operational limit in overall temperature range |
| Current, relative to input area | +/- 0,6 % |
| Basic error limit (operational limit at 25 °C) |
| Current, relative to input area | +/- 0,4 % |
| Interference voltage suppression for f = n x (fl +/- 1%), fl = interference frequency |
| Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
| Isochronous mode |
| Isochronous operation (application synchronized up to terminal) | No |
| Interrupts/diagnostics/status information |
| Diagnostic messages |
| Wire break | Yes |
| Group error | Yes |
| Overflow/underflow | Yes |
| Diagnostics indication LED |
| Group error SF (red) | Yes |
| Parameter |
| Measurement type/range | deactivated / 4 to 20 mA |
| Group diagnostics | Disable / enable |
| Overflow/underflow | Disable / enable |
| Galvanic isolation |
| Galvanic isolation analog inputs |
| between the channels | No |
| between the channels and the backplane bus | Yes |
| between the channels and the load voltage L+ | No |
| Isolation |
| Isolation checked with | 500 V DC |
| Standards, approvals, certificates |
| CE mark | Yes |
| UL approval | Yes |
| Ambient conditions |
| Extended ambient conditions |
| Relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
| Relative humidity |
| with condensation / maximum | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
| Resistance |
| to biologically active substances / conformity with EN 60721-3-3 | Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| to chemically active substances / conformity with EN 60721-3-3 | Yes; , Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| to mechanically active substances / conformity with EN 60721-3-3 | Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
| Mechanical and climatic conditions during operation |
| Climatic conditions in operation |
| Temperature |
| Min. | -25 °C; = Tmin |
| max. | 60 °C; = Tmax |
| Dimensions |
| Width | 15 mm |
| Height | 81 mm |
| Depth | 52 mm |
| Weight |
| Weight, approx. | 40 g |
| Status | Apr 9, 2012 |