| | SIPLUS HMI KTP1000 BASIC COLOR DP 10.4" FOR MEDIAL STRESS WITH CONFORMAL COATING BASED ON 6AV6647-0AE11-3AX0 |
| |
| General information |
| Customer-specific configuration | Yes |
| Display |
| Design of display | TFT |
| Screen diagonal | 10.4 in |
| Size | 10.4" (211.2 mm x 158.4 mm) |
| Display type | TFT, 256 Farben |
| Color type | Colors |
| Resolution (pixels) |
| Horizontal image resolution | 640 |
| Vertical image resolution | 480 |
| Resolution (WxH in pixel) | 640 x 480 |
| Backlighting |
| MTBF backlighting (at 25 °C) | about 50000 hours |
| Control elements |
| Control elements | Membrane keyboard |
| Operating mode |
| Operating options | Keys and Touch |
| Function keys, programmable | 8 function keys |
| Connection for mouse/keyboard/barcode reader | - / - / - |
| Keyboard fonts |
| Keys with LED | No |
| Number of function keys with LEDs | 0 |
| Numeric/alphabetical input | Yes (on-screen keyboard) / Yes (on-screen keyboard) |
| hexadecimal keyboard | Yes; Onscreen keyboard |
| Multi-key operation | No |
| Touch operation |
| Touch screen | Analog, resistive |
| Touch screen (analog/resistive) | Yes |
| Supply voltage |
| Supply voltage | 24 V DC |
| Input current |
| Rated current | 0.6 A |
| Inrush current A²s | 0.2 A²·s |
| Power |
| Power | 15 W |
| Processor |
| Processor | RISC 32-bit, 200 MHz |
| Processor type | RISC 32-bit |
| other | No |
| Memory |
| Type | Flash / RAM |
| Usable memory for user data | 1024 KB usable memory for user data |
| Type of output |
| Info LED | No |
| Power LED | No |
| Error LED | No |
| Time of day |
| Clock |
| Type | Software clock, no battery backup |
| Interfaces |
| Interfaces | 1 x RS422,1 x RS485 (max. 12 Mbit/s) |
| Number of RS 485 interfaces | 1 |
| Transmission rate, max. | 12 Mbit/s |
| USB port | No |
| PC card slot | No |
| CF card slot | No |
| Multi Media Card slot | No |
| Number of parallel interfaces | 0 |
| Special interfaces | No |
| Industrial Ethernet |
| Industrial Ethernet interface | No |
| Industrial Ethernet status LED | 0 |
| Protocols |
| PROFINET | No |
| Protocols (Ethernet) |
| TCP/IP | No |
| Protocols (terminal link) |
| Sm@rtAccess | No |
| Further protocols |
| PROFIBUS | Yes |
| MPI | Yes |
| MODBUS | Yes |
| Ambient conditions |
| Mounting position | vertical |
| maximum permissible angle of inclination without external ventilation | +/- 35 ° |
| Storage/transport temperature |
| Transport, storage | -20 °C to +60 °C |
| Relative humidity |
| max. relative humidity | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
| Extended ambient conditions |
| Relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
| Resistance |
| to biologically active substances / conformity with EN 60721-3-3 | Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| to chemically active substances / conformity with EN 60721-3-3 | Yes; , Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation! |
| to mechanically active substances / conformity with EN 60721-3-3 | Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
| Degree and class of protection |
| Front | IP65 |
| Type of protection | IP20 |
| IP (at the front) | IP65 |
| Rear | IP20 |
| Standards, approvals, certificates |
| Certifications | CE |
| FM Class I Div. 2 | No |
| GL | No |
| ABS | No |
| BV | No |
| DNV | No |
| LRS | No |
| Class NK | No |
| PRS | No |
| Gost-R | No |
| Suitable for safety functions | No |
| Use in hazardous areas |
| EX zone 2 | No |
| EX zone 22 | No |
| Configuration |
| Message indicator | Yes |
| With alarm logging system (incl. buffer and acknowledgment) | Yes |
| Process value display (output) | Yes |
| Process value default (input) possible | Yes |
| Recipe administration | Yes |
| Configuration software |
| Configuration tool | WinCC flexible Compact Version 2008 or higher (to be ordered separately) |
| 2nd configuration kit | WinCC flexible Compact |
| Version | Version 2008 |
| Configuration tool | WinCC flexible |
| Type | Compact |
| Languages |
| Online languages |
| Number of online/runtime languages | 5 |
| Languages |
| Languages per project | 32 |
| Functionality under WinCC flexible |
| Libraries | Yes |
| Number of Visual Basic Scripts | Not possible |
| Debugging in the simulator | No |
| Task planner | Yes |
| Help system | Yes |
| Number of characters per info text | 320 |
| With alarm logging system (incl. buffer and acknowledgment) |
| Number of alarm classes | 32 |
| Number of messages | 200 |
| Bit messages |
|