| | SIPLUS S7-200 TD400C -10 ... +60 DEGREES C BASED ON 6AV6640-0AA00-0AX1 |
| |
| Display |
| Design of display | STN |
| Screen diagonal | 3.7 in; 4-line |
| Size | 3.7" |
| Display type | STN, Schwarz/Weiss |
| Color type | Black/white |
| Resolution (pixels) |
| Horizontal image resolution | 192 |
| Vertical image resolution | 64 |
| Resolution (WxH in pixel) | 192 x 64 |
| Backlighting |
| MTBF backlighting (at 25 °C) | Approx. 20,000 hours |
| Control elements |
| Control elements | Membrane keyboard |
| Operating mode |
| Operating options | Keys |
| Function keys, programmable | 15 function keys |
| Keyboard fonts |
| Number of configurable system keys | 15 |
| System keys | Yes |
| Supply voltage |
| Supply voltage | 24 V DC |
| Memory |
| Usable memory for user data | No info |
| Interfaces |
| Interfaces | 1 x RS485 (max. 187.5 Mbit/s) |
| Number of RS 485 interfaces | 1 |
| Transmission rate, max. | 187.5 Mbit/s |
| Number of parallel interfaces | 0 |
| Protocols |
| Protocols (Ethernet) |
| TCP/IP | No |
| Further protocols |
| PROFIBUS | No |
| MPI | Yes |
| AS-i | No |
| CAN | No |
| INTERBUS | No |
| MODBUS | No |
| Data highway | No |
| DeviceNet | No |
| Local Operating Network | No |
| SUCOnet | No |
| other bus systems | Yes |
| Ambient conditions |
| Operating temperature |
| Operation | -10 °C to +60 °C |
| Storage/transport temperature |
| Transport, storage | -20 °C to +60 °C |
| Extended ambient conditions |
| Relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
| Relative humidity |
| with condensation / maximum | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
| Resistance |
| to biologically active substances / conformity with EN 60721-3-3 | Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| to chemically active substances / conformity with EN 60721-3-3 | Yes; , Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| to mechanically active substances / conformity with EN 60721-3-3 | Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
| Degree and class of protection |
| Front | IP65, NEMA 4, NEMA 4x, NEMA 12 (when installed) |
| Type of protection | IP20 |
| IP (at the front) | IP65 |
| NEMA | NEMA 4, NEMA 4x, NEMA 12 |
| Rear | IP20 |
| Standards, approvals, certificates |
| Certifications | CE, KC, Gost R, NEMA 4, NEMA 4x, NEMA 12 |
| KC approval | Yes |
| Configuration |
| Process value display (output) | No |
| Process value default (input) possible | No |
| Configuration software |
| Configuration tool | MicroWin (to be ordered separately) |
| 1st configuration kit | MicroWin |
| Configuration tool | MicroWin |
| Languages |
| Languages |
| Languages per project | 2 |
| Functionality under WinCC flexible |
| Security |
| Number of user groups | 1 |
| Weight |
| Weight | 0.33 kg |
| Status | Mar 12, 2012 |