| | SIPLUS ET200S PM-E DC 24V WITH DIAGNOSTICS -40 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7138-4CA01-0AA0 |
| |
| Supply voltage |
| Load voltage L+ |
| Rated value (DC) | 24 V |
| Short-circuit protection | No; external (e.g. automatic circuit breaker), tripping characteristic C |
| Reverse polarity protection | Yes |
| Input current |
| from load voltage 1L+ (without load), max. | 4 mA |
| Current carrying capacity |
| Current carrying capacity up to 60 °C, max. | 10 A |
| Power losses |
| Power loss, typ. | 0.1 W |
| Interrupts/diagnostics/status information |
| Diagnostic messages |
| Diagnostics | Yes |
| Missing load voltage | Yes |
| Diagnostics indication LED |
| Rated load voltage PWR (green) | Yes |
| Group error SF (red) | Yes |
| Parameter |
| Remark | 3 bytes |
| Missing load voltage | Disable / enable |
| Galvanic isolation |
| primary/secondary | Yes; between rated load voltage and backplane bus, between power modules |
| Isolation |
| Isolation checked with | 500 V DC |
| Ambient conditions |
| Extended ambient conditions |
| Relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
| Relative humidity |
| with condensation / maximum | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
| Resistance |
| to biologically active substances / conformity with EN 60721-3-3 | Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| to chemically active substances / conformity with EN 60721-3-3 | Yes; , Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation! |
| to mechanically active substances / conformity with EN 60721-3-3 | Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
| Mechanical and climatic conditions during operation |
| Climatic conditions in operation |
| Temperature |
| Min. | -40 °C; = Tmin |
| max. | 70 °C; = Tmax |
| Standards, approvals, certificates |
| CE mark | Yes |
| UL approval | Yes |
| Dimensions |
| Width | 15 mm |
| Height | 81 mm |
| Depth | 52 mm |
| Weight |
| Weight, approx. | 35 g |
| Status | Mar 12, 2012 |