| | SIPLUS ET200S EM 2RO DC24V-AC230V/5A -25 ... +70 DEGREES C BASED ON 6ES7132-4HB01-0AB0 5 PIECES PER PACKAGING UNIT . ELECTRON. MODULES FOR ET 200S, 2 DO RELAY 24V DC - 230V AC/5A,15 MM WIDTH FIRST-UP SIGNAL WITH LED SF (GROUP FAULT), |
| |
| Supply voltage |
| Load voltage L+ |
| Rated value (DC) | 24 V; From power module |
| Reverse polarity protection | Yes |
| Input current |
| from load voltage L+ (without load), max. | 30 mA |
| from backplane bus 3.3 V DC, max. | 10 mA |
| Power losses |
| Power loss, typ. | 0.6 W |
| Address area |
| Address space per module |
| with packing | 2 bit |
| without packing | 1 byte |
| Digital outputs |
| Number/binary outputs | 2 |
| Functionality/short-circuit strength | No; external fuse, max. 6 A quick-acting |
| Limitation of inductive shutdown voltage to | No |
| Controlling a digital input | Yes |
| Output current |
| for signal "1" rated value | 5 A |
| for signal "1" minimum load current | 8 mA |
| Parallel switching of 2 outputs |
| for increased power | No |
| for redundant control of a load | No |
| Switching frequency |
| with resistive load, max. | 2 Hz |
| with inductive load, max. | 0.5 Hz |
| on lamp load, max. | 2 Hz |
| Relay outputs |
| Switching capacity of contacts |
| Thermal continuous current, max. | 5 A |
| Cable length |
| Cable length, shielded, max. | 1000 m |
| Cable length unshielded, max. | 600 m |
| Isochronous mode |
| Isochronous operation (application synchronized up to terminal) | No |
| Interrupts/diagnostics/status information |
| Substitute values connectable | Yes; 0/1 |
| Diagnostic messages |
| Diagnostic functions | No |
| Diagnostics indication LED |
| Status indicator digital output (green) | Yes |
| Parameter |
| Remark | 3 bytes |
| Behavior on CPU/Master STOP, channel-wise | Substitute a value/keep last value |
| Galvanic isolation |
| Galvanic isolation digital outputs |
| between the channels | Yes |
| between the channels and the backplane bus | Yes |
| between the channels and the load voltage L+ | Yes |
| Isolation |
| tested with |
| Channels against backplane bus and load voltage L+ | 1500 V AC |
| Load voltage L+ against backplane bus | 500 V DC |
| Ambient conditions |
| Extended ambient conditions |
| Relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
| Relative humidity |
| with condensation / maximum | 100 %; , incl. condensation / frost permitted (no commissioning under condensation conditions) |
| Resistance |
| to biologically active substances / conformity with EN 60721-3-3 | Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! |
| to chemically active substances / conformity with EN 60721-3-3 | Yes; , Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| to mechanically active substances / conformity with EN 60721-3-3 | Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
| Dimensions |
| Width | 15 mm |
| Height | 81 mm |
| Depth | 52 mm |
| Weight |
| Weight, approx. | 50 g |
| Status | Mar 12, 2012 |