| | Similar to image | | CIRCUIT BREAKER 400V 6KA, 3POLE, B, 6A |
| |
| Technical data: | | |
| Current / for AC / rated value | A | 6 |
| Tripping characteristic class | | B |
| type of voltage | | AC/DC |
| Supply voltage | | |
| | V | 400 |
- with single-phase operation / with AC / rated value
| V | 230 |
- with multi-phase operation / with AC / rated value
| V | 400 |
| Operating voltage | | |
| | V | 24 |
- with single-phase operation / with AC / maximum
| V | 250 |
- with multi-phase operation / with AC / maximum
| V | 440 |
- for DC / rated value / maximum
| V | 60 |
| Supply voltage frequency / rated value | Hz | 50 |
| Number of poles | | 3 |
| Number of poles /note | | 3P |
| Switching capacity current | | |
- in accordance with IEC 60947-2 / rated value
| kA | 6 |
- acc. to EN 60898 / rated value
| kA | 6 |
| Number of pitch units for width | | 3 |
| Product extension / can be installed / supplementary device | | Yes |
| Product feature / sealable | | Yes |
| Built in orientation | | any |
| Protection class IP | | IP20, with connected conductors |
| Degree of pollution | | 2 |
| Ambient temperature | | |
| | °C | -25 |
| | °C | 45 |
| Influence of the surrounding temperature | | Periodically +55°C, max. 95% humidity |
| Ambient temperature / during storage | | |
| | °C | -40 |
| | °C | 75 |
| Mechanical operating cycles as operating time / typical | | 20,000 |
| Resistance against vibration / according to IEC 60068-2-6 | | 50 at 25 to 150 Hz and 60 at 35 Hz (4 sec) |
| Product equipment / touch-protection | | Yes |
| Insulation voltage | | |
- with single-phase operation / with AC / rated value
| V | 250 |
- with multi-phase operation / with AC / rated value
| V | 440 |
| Section de conducteur raccordable | | |
| | | |
| | mm? | 0.75 |
| | mm? | 35 |
| | | |
| | mm? | 0.75 |
| | mm? | 35 |
- finely stranded / with wire end processing
| | |
| | mm? | 0.75 |
| | mm? | 25 |
| Tightening torque / with screw-type terminals | | |
| | N·m | 2.5 |
| | N·m | 3 |
| Product feature | | |
- [not supplied - silicon-free]
| | Yes |
| | | Yes |
| Number of test cycles / for environmental testing / in accordance with IEC 60068-2-30 | | 6 |
| |
| Certificates/approvals: |
| General Product Approval | Declaration of Conformity | other | | CEBEC | ROSTEST | | |
| |
| |
| last change: | Aug 26, 2011 |