4CQ5070-0JE0 - COLUMN ROTARY TRANSFORMER; PHASES:3; PN(KVA):41,7; UPRI(V):400; USEC(V):0-400; ISEC(A):60; F(HZ):50...400; VECTOR GR./SHIELD WNG.:YNA0 /0; TA/ISOKL:40 /E; IP20; MANUAL OPERATION; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLATION:PLACE; VDE 0552 (siemens) - Quad Industry GmbH

Артикул: 4CQ5070-0JE0
Наименование: COLUMN ROTARY TRANSFORMER; PHASES:3; PN(KVA):41,7; UPRI(V):400; USEC(V):0-400; ISEC(A):60; F(HZ):50...400; VECTOR GR./SHIELD WNG.:YNA0 /0; TA/ISOKL:40 /E; IP20; MANUAL OPERATION; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLATION:PLACE; VDE 0552 (siemens)
Производитель: Siemens


Наименование продукта
COLUMN ROTARY TRANSFORMER; PHASES:3; PN(KVA):41,7; UPRI(V):400; USEC(V):0-400; ISEC(A):60; F(HZ):50...400; VECTOR GR./SHIELD WNG.:YNA0 /0; TA/ISOKL:40 /E; IP20; MANUAL OPERATION; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLATION:PLACE; VDE 0552
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2001-01-01 2011-01-01 2011-01-01 2011-01-01
    Версия от 2011-11-23
 
COLUMN ROTARY TRANSFORMER; PHASES:3; PN(KVA):41,7; UPRI(V):400; USEC(V):0-400; ISEC(A):60; F(HZ):50...400; VECTOR GR./SHIELD WNG.:YNA0 /0; TA/ISOKL:40 /E; IP20; MANUAL OPERATION; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLATION:PLACE; VDE 0552
 
General technical data:
product designation   4CQ5070-0JE0
Product brand name   SIDAC
Operating apparent output / for harsh operating conditions / rated value V·A 41.7
Operating apparent output / rated value kV·A 48
Manner of switching for transformers   Yna0
Verification of suitability   CE
Product function / temperature surveillance   No
 
Inputs:
Phase number / of the inputs   3
Input voltage / _1 / rated value V 400
Electrical input frequency    
  • minimum
Hz 50
  • maximum
Hz 400
 
Outputs:
Phase number / of the outputs   3
Output voltage    
  • maximum
V 400
  • minimum
V 0
Output current    
  • maximum
A 69.3
  • minimum
A 0
  • for harsh operating conditions / maximum
A 60
Electrical output frequency    
  • maximum
Hz 400
  • minimum
Hz 50
 
Ambient conditions:
Thermal class / according to IEC 60085   E
Ambient temperature / rated value °C 40
Protection class IP   IP20
 
Mechanical design:
Design of the electrical connection    
  • at the input / for main current circuit
  screw-type terminals
  • secondary side / for main current circuit
  screw-type terminals
Execution of the actuating drive   manual operation
Type of mounting   installation
Width m 0.514
Height m 1.2
Depth m 0.49
 
Certificates/approvals:
   
General Product Approval other
ROSTEST other        
 
Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
http://www.siemens.com/industrial-controls/mall
CAx-Online-Generator
http://www.siemens.com/cax
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
http://support.automation.siemens.com/WW/view/en/4CQ5070-0JE0/all
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=4CQ5070-0JE0
 
 
 
last change:
Aug 19, 2011

Назад в раздел