4AM6442-5BU10-0FA1 - TRANSFORMER SITAS; PHASES:1; PN/PN(S6)(KVA):2 /9,7; UPRI(V):415+/-5%; USEC(V):240; ISEC(A):8,333; F(HZ):50...60; VECTOR GR./SHIELD WNG.:II0 /0; TA/ISOKL:40 /B; IP00; TYPE OF TERMINALS:CAGE-CLAMP; INSTALLATION:SCREW; EN 61558-2-2, -2-4>CONTROL CIRCUIT TRANSFORMER< >ISOLATION TRANSFORMER< (siemens) - Quad Industry GmbH

Артикул: 4AM6442-5BU10-0FA1
Наименование: TRANSFORMER SITAS; PHASES:1; PN/PN(S6)(KVA):2 /9,7; UPRI(V):415+/-5%; USEC(V):240; ISEC(A):8,333; F(HZ):50...60; VECTOR GR./SHIELD WNG.:II0 /0; TA/ISOKL:40 /B; IP00; TYPE OF TERMINALS:CAGE-CLAMP; INSTALLATION:SCREW; EN 61558-2-2, -2-4>CONTROL CIRCUIT TRANSFORMER< >ISOLATION TRANSFORMER< (siemens)
Производитель: Siemens


Наименование продукта
TRANSFORMER SITAS; PHASES:1; PN/PN(S6)(KVA):2 /9,7; UPRI(V):415+/-5%; USEC(V):240; ISEC(A):8,333; F(HZ):50...60; VECTOR GR./SHIELD WNG.:II0 /0; TA/ISOKL:40 /B; IP00; TYPE OF TERMINALS:CAGE-CLAMP; INSTALLATION:SCREW; EN 61558-2-2, -2-4>CONTROL CIRCUIT TRANSFORMER< >ISOLATION TRANSFORMER<
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2001-01-01 2012-01-01 2012-02-01 2012-02-01
TRANSFORMER SITAS; PHASES:1; PN/PN(S6)(KVA):2 /9,7; UPRI(V):415+/-5%; USEC(V):240; ISEC(A):8,333; F(HZ):50...60; VECTOR GR./SHIELD WNG.:II0 /0; TA/ISOKL:40 /B; IP00; TYPE OF TERMINALS:CAGE-CLAMP; INSTALLATION:SCREW; EN 61558-2-2, -2-4 >CONTROL CIRCUIT TRANSFORMER< >ISOLATION TRANSFORMER<
 
General technical details:
product designation   transformer SITAS
product brand name   SIDAC
Operating apparent output / rated value V·A 2,000
Efficiency   0.96
Manner of switching for transformers   Ii0
Verification of suitability   CE
Product function    
  • temperature surveillance
  No
  • isolation control
  No
  • short circuit and overload protection
  No
Number of the protective coils   0
Short-term vector power V·A 9,700
Relative short-circuit voltage % 2.23
 
Inputs:
Phase number / of the inputs   1
Input voltage    
  • _1 / rated value
V 436
  • _2 / rated value
V 415
  • _3 / rated value
V 394
Electrical input frequency    
  • minimum
Hz 50
  • maximum
Hz 60
 
Outputs:
Phase number / of the outputs   1
Output voltage    
  • _1 / rated value
V 240
Electrical output frequency    
  • maximum
Hz 60
  • minimum
Hz 50
 
Ambient conditions:
Thermal class / according to IEC 60085   B
Ambient temperature / rated value °C 40
Protection class IP   IP00
 
Mechanical design:
Design of the electrical connection    
  • secondary side / for main current circuit
  Cage-Clamp terminals
  • at the input / for main current circuit
  Cage Clamp terminals
Type of mounting   screws
Construction form of the iron core   EI 174/102
Width m 0.176
Height m 0.164
Depth m 0.158
 
Certificates/approvals:
   
General Product Approval Shipping Approval other
GOST PRS / Polski Rejestr Statkow Confirmation other    
 
Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
http://www.siemens.com/industrial-controls/mall
CAx-Online-Generator
http://www.siemens.com/cax
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
http://support.automation.siemens.com/WW/view/en/4AM6442-5BU10-0FA1/all
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=4AM6442-5BU10-0FA1
 
 
 
last change:
Dec 5, 2011

Назад в раздел