| | DIGITAL MONITORING RELAY COS-PHI AND CURRENT MONITORING FOR IO-LINK 90 TO 690V AC, 0.2 TO 10A OVERSHOOT AND UNDERSHOOT ON DELAY TIME TRIPPING DELAY TIME HYSTERESIS 0.1 TO 3.0A 2 CHANGE-OVER CONTACTS, SPRING-LOADED TERMINAL |
| Product function | | Active power monitoring relay |
| |
| Measuring circuit: | | |
| Number of poles / for main current circuit | | 1 |
| Phase number | | 1 |
| Adaptable response value phase angle | ° | 0.1… 0.99 |
| Type of current / for monitoring | | AC |
| Measurable current | A | 0.2… 10 |
| Adjustable response current | | |
| | A | 0.2… 10 |
| | A | 0.2… 10 |
| Adjustable response delay time | | |
| | s | 0… 999.9 |
- with lower or upper limit violation
| s | 0… 999.9 |
| Adjustable switching hysteresis for measured current value | mA | 0… 3,000 |
| Operating voltage | | |
| | V | 90… 690 |
| Relative metering precision | % | 10 |
| Precision of digital display | | +/-1 digit |
| Relative repeat accuracy | % | 1 |
| |
| General technical details: |
| Design of the display | | LCD |
| Product function | | |
- overcurrent recognition of 1 phase
| | Yes |
- undercurrent recognition of 1 phase
| | Yes |
| | | Yes |
- open-circuit or closed-circuit current principle
| | Yes |
| Starting time / after the control supply voltage has been applied | ms | 1,000 |
| Type of voltage / of the controlled supply voltage | | DC |
| Control supply voltage | | |
| | | |
| | V | 0… 0 |
| | | |
| | V | 0… 0 |
| | | |
| | V | 24… 24 |
| Working range factor supply voltage rated value | | |
| | | 0.75… 1.25 |
| Impulse voltage resistance / rated value | kV | 6 |
| Recorded real power | W | 2 |
| Protection class IP | | IP20 |
| Electromagnetic compatibility | | IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4 |
| Resistance against vibration / according to IEC 60068-2-6 | | 1
6 Hz: 15 mm, 6
500 Hz: 2g |
| Resistance against shock / according to IEC 60068-2-27 | | sinusoidal half-wave 15g / 11 ms |
| Installation altitude / at a height over sea level / maximum | m | 2,000 |
| Conductor-bound parasitic coupling BURST / according to IEC 61000-4-4 | | 2 kV |
| Conductor-bound parasitic coupling conductor-earth SURGE / according to IEC 61000-4-5 | | 2 kV |
| Conductor-bound parasitic coupling conductor-conductor SURGE / according to IEC 61000-4-5 | | 1 kV |
| Electrostatic discharge / according to IEC 61000-4-2 | | 6 kV contact discharge / 8 kV air discharge |
| Field-bound parasitic coupling / according to IEC 61000-4-3 | | 10 V/m |
| Degree of pollution | | 2 |
| Ambient temperature | | |
| | °C | -25… +60 |
| | °C | -40… +85 |
| | °C | -40… +85 |
| Galvanic isolation | | |
- between entrance and outlet
| | Yes |
| | | Yes |
- between the voltage supply and other circuits
| | Yes |
| Mechanical operating cycles as operating time / typical | | 10,000,002 |
| Electrical operating cycles as operating time / at AC-15 / at 230 V / typical | | 100,000 |
| Operating cycles / with 3RT2 contactor / maximum | 1/h | 5,000 |
| |
| Communication: | | |
| Type of voltage supply / via input/ output link master | | Yes |
| IO-Link transfer rate | | COM2 (38,4 kBaud) |
| Protocol / will be supported / IO-Link protocol | | Yes |
| Data volume | | |
- of the address range of the outputs / with cyclical transfer
| byte | 2 |
- of the address range of the inputs / with cyclical transfer
| byte | 4 |
| Point-to-point cycle time / between master and IO-Link device / minimum | ms | 10 |
| |
| Mechanical design: |
| Width | mm | 22.5 |
| Height | mm | 103 |
| Depth | mm | 91 |
| Built in orientation | | any |
| Distance, to be maintained, to earthed part | | |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| Distance, to be maintained, to the ranks assembly | | |
| | mm | <
|