| BASIC UNIT 1 SIMOCODE PRO C; PROFIBUS DP-INTERFACE 12 MBIT/S, RS485; 4I/3O FREELY PARAMETERIZABLE; US: DC 24V; THERMISTOR MOTOR PROTECTION; OUTPUTS MONOSTABLE |
|
General technical data: |
product brand name | | SIRIUS |
Protection class IP | | IP20 |
Built in orientation | | any |
EMC immunity to interference / according to IEC 60947-1 | | corresponds to degree of severity 3 |
Conductor-bound parasitic coupling BURST / according to IEC 61000-4-4 | | 2 kV (power ports) / 1 kV (signal ports) |
Conductor-bound parasitic coupling conductor-earth SURGE / according to IEC 61000-4-5 | | 2 kV |
Conductor-bound parasitic coupling conductor-conductor SURGE / according to IEC 61000-4-5 | | 1 kV |
Field-bound parasitic coupling / according to IEC 61000-4-3 | | 10 V/m |
EMC emitted interference / according to IEC 60947-1 | | class A |
Resistance against vibration | | 1-6 Hz / 15 mm; 6-500 Hz / 2 g |
Impulse voltage resistance / rated value | V | 4,000 |
Insulation voltage / rated value | V | 300 |
Active power loss / total / typical | W | 5 |
Switching behaviour | | monostable |
Number of outputs | | 3 |
Number of inputs | | 4 |
Number of semiconductor outputs | | 0 |
Number of outputs / as contact-affected switching element | | 3 |
Product component | | |
- input for thermistor connection
| | Yes |
- input for analog temperature sensors
| | No |
- input for ground-fault detection
| | No |
Product function | | |
| | No |
| | Yes |
Item designation | | |
- according to DIN EN 61346-2
| | F |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | F |
|
Communication: |
Product function | | |
| | Yes |
Protocol / will be supported / PROFIBUS DP protocol | | Yes |
|
Main circuit: |
Operating voltage | | |
| V | 24… 24 |
|
Supply voltage: |
Type of voltage | | |
| | DC |
|
Control circuit: |
Type of voltage | | |
- of the controlled supply voltage
| | DC |
Control supply voltage | | |
| V | 24 |
| V | 24… 24 |
|
Installation/mounting/dimensions: |
Type of mounting | | screw and snap-on mounting |
Width | mm | 45 |
Height | mm | 111 |
Depth | mm | 95 |
|
Connections: |
Product function | | |
- removable terminal for auxiliary and control circuit
| | Yes |
Design of the electrical connection | | |
- for auxiliary and control current circuit
| | screw-type terminals |
Conductor cross-section that can be connected / for auxiliary contact | | |
| mm² | 0.5… 4 |
| | |
- with conductor end processing
| mm² | 0.5… 2.5 |
- without conductor final cutting
| mm² | 0.5… 2.5 |
AWG number / as coded connectable conductor cross-section | | |
| | 20… 14 |
|
Ambient conditions: |
Installation altitude / at a height over sea level / maximum | m | 4,000 |
Ambient temperature | | |
| °C | -40… +80 |
| °C | -25… +60 |
| °C | -40… +80 |
Relative humidity / during operating phase | % | 5… 95 |
|
Certificates/approvals: |
Verification of suitability | | CE / UL / CSA / CCC / C-TICK / GOST / NOM / ATEX / NEPSI / ABS / DNV / GL / LRS / RoHS |
General Product Approval | For use in hazardous locations | | |
| |
|
last change: | Mar 12, 2012 |