| | SIRIUS POSITION SWITCH; PLASTIC HOUSING ACC. TO EN50047, 50MM DEVICE CONNECTION 2X(M20X1.5); 1NO/1NC SNAP-ACTION CONTACTS ROLLER LEVER W. PLASTIC ROLLER 19MM |
| Manufacturer article number / of the basic unit included in the scope of supply | 3SE5242-0HC05 |
| Manufacturer article number / of the actuator head for position switches included in the scope of supply | 3SE5000-0AK00 |
| Manufacturer article number / of the operating lever included in the scope of supply | 3SE5000-0AA21 |
| General technical details: | |
| Product designation | standard position switch |
| Insulation voltage | |
| | 400 V |
| Degree of pollution | class 3 |
| Thermal current | 6 A |
| Operating current | |
| | |
| | 6 A |
| | 6 A |
| | 3 A |
| | |
| | 3 A |
| | 0.55 A |
| | 0.27 A |
| Continuous current | |
- of the slow DIAZED fuse link
| 6 A |
- of the quick DIAZED fuse link
| 10 A |
- of the C characteristic circuit breaker
| 2 A |
| Mechanical operating cycles as operating time | |
| | 15000000 |
| Electrical operating cycles as operating time / with contactor 3RH11, 3RT1016, 3RT1017, 3RT1024, 3RT1025, 3RT1026 | |
| | 1000000 |
| Electrical operating cycles as operating time / at AC-15 / at 230 V | |
| | 100000 |
| Electrical operating cycles in one hour | |
- with contactor 3RH11, 3RT1016, 3RT1017, 3RT1024, 3RT1025, 3RT1026
| 6000 |
| Repeat accuracy | 0.1 mm |
| Design of the contact element | snap-action contacts |
| number of NC contacts | |
| | 1 |
| Design of the switching function | positive opening, integrated |
| number of NO contacts | |
| | 1 |
| Resistance against vibration | 0,35 mm / 5g |
| Resistance against shock | 30g / 11 ms |
| ambient temperature | |
- during the operating phase
| |
| | -25 °C |
| | 85 °C |
| | |
| | -40 °C |
| | 90 °C |
| Width of the sensor | 50 mm |
| Material | |
| | plastic |
| Material / of the housing / of the switch head | plastic enclosure |
| design of the operating mechanism | metal lever, 21 mm long, straight, plastic roller 19 mm |
| Actuating speed | |
| | 0.1 m/s |
| | 3 m/s |
| Protection class IP | IP66/IP67 |
| built in orientation | any |
| Design of the cable entry (gland) | 2 x (M20 x 1.5) |
| Design of the electrical connection | screw-type terminals |
| | |
| |
| |
| |
| last change: | 08/11/2008 |