| | SIRIUS SOFT STARTER, WITH BRAKE FUNCTION, MOTOR-INTEGRATED, IP 54, 29A, 15KW/400V, 40DEGREES, 400-575V AC, 24V DC, PLUG-IN TERMINAL |
| |
| General details: |
| product brand name | | SIRIUS |
| Product equipment | | |
- integrated bridging contact system
| | Yes |
| | | Yes |
| Product function | | |
- motor overload protection
| | No |
- evaluation of thermal resistor motor protection
| | Yes |
| | | No |
| Item designation | | |
- according to DIN EN 61346-2
| | Q |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | G |
| |
| Power Electronics: |
| product designation | | soft starters for standard applications |
| Operating current | | |
| | A | 29 |
| Emitted mechanical power / for three-phase servomotors | | |
- at 400 V / at standard switching / at 40 °C
| | |
| | W | 15,000 |
- at 500 V / at standard switching / at 40 °C
| | |
| | W | 18,500 |
| Operating frequency | | |
| | Hz | 50… 60 |
| Relative negative tolerance / of the operating frequency | % | -10 |
| Relative positive tolerance / of the operating frequency | % | 10 |
| Operating voltage / with standard circuit / rated value | V | 400… 575 |
| Minimum load in % of l_M | % | 15 |
| Continuous operating current in % of l_e / at 40°C | % | 115 |
| Active power loss / at operating current / at 40°C / during operating phase / typical | W | 21 |
| |
| Control electronics: |
| Type of voltage / of the controlled supply voltage | | AC/DC |
| Control supply voltage / 1 | | |
| | V | 24 |
| | V | 24 |
| Control supply voltage / 1 / for DC / rated value | V | 24 |
| |
| Mechanical design: |
| Width | mm | 252 |
| Height | mm | 187 |
| Depth | mm | 85 |
| Type of mounting | | direct mounting |
| Altitude of installation site / at a height over sea level | m | 2,000 |
| Number of poles / for main current circuit | | 3 |
| |
| Electrical connections: |
| Design of the electrical connection | | |
| | | tab connection |
- for auxiliary and control current circuit
| | tab connection |
| Number of NC contacts / for auxiliary contacts | | 3 |
| Number of NO contacts / for auxiliary contacts | | 1 |
| Number of change-over switches / for auxiliary contacts | | 0 |
| |
| Ambient conditions: |
| Ambient temperature | | |
| | °C | -25… +40 |
| | °C | -25… +80 |
| Derating temperature | °C | 40 |
| Protection class IP | | IP54 |
| |
| Certificates/approvals: | | |
| General Product Approval | other | | ROSTEST | Manufacturer | | | | | |
| |
| |
| Further information: |
| Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/industrial-controls/catalogs |
| Industry Mall (Online ordering system) http://www.siemens.com/industrial-controls/mall |
| CAx-Online-Generator http://www.siemens.com/cax |
| Service&Support (Manuals, Certificates, Characteristics, FAQs,...) http://support.automation.siemens.com/WW/view/en/3RW4201-8RB25-1KW0/all |
| Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...) http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3RW4201-8RB25-1KW0 |
| |
| |
| | |
| |
| last change: | Oct 28, 2011 |