| | SIRIUS SOFT STARTER, S12, 280 A, 200 KW/500 V, 40 DEG., 400-600 V AC, 230 V AC, CAGE CLAMP TERMINALS |
| |
| General details: |
| product brand name | | SIRIUS |
| Product equipment | | |
- integrated bridging contact system
| | Yes |
| | | Yes |
| Product function | | |
- intrinsic device protection
| | Yes |
- motor overload protection
| | Yes |
- evaluation of thermal resistor motor protection
| | No |
| | | Yes |
- adjustable current limitation
| | Yes |
| | | No |
| Product component / outlet for enine brake | | No |
| Item designation | | |
- according to DIN EN 61346-2
| | Q |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | G |
| |
| Power Electronics: |
| product designation | | soft starters for standard applications |
| Operating current | | |
| | A | 280 |
| | A | 248 |
| | A | 215 |
| Emitted mechanical power / for three-phase servomotors | | |
- at 400 V / at standard switching / at 40 °C
| | |
| | W | 160,000 |
- at 500 V / at standard switching / at 40 °C
| | |
| | W | 200,000 |
| Operating frequency | | |
| | Hz | 50… 60 |
| Relative negative tolerance / of the operating frequency | % | -10 |
| Relative positive tolerance / of the operating frequency | % | 10 |
| Operating voltage / with standard circuit / rated value | V | 400… 600 |
| Relative negative tolerance / of the operating voltage / with standard circuit | % | -15 |
| Relative positive tolerance / of the operating voltage / with standard circuit | % | 10 |
| Minimum load in % of l_M | % | 20 |
| Adjustable rated current / of the motor / for motor overload protection / minimum | A | 130 |
| Continuous operating current in % of l_e / at 40°C | % | 115 |
| Active power loss / at operating current / at 40°C / during operating phase / typical | W | 90 |
| |
| Control electronics: |
| Type of voltage / of the controlled supply voltage | | AC |
| Control supply voltage frequency / 1 / rated value | Hz | 50 |
| Control supply voltage frequency / 2 / rated value | Hz | 60 |
| Relative negative tolerance / of the control supply voltage frequency | % | -10 |
| Relative positive tolerance / of the control supply voltage frequency | % | 10 |
| Control supply voltage / 1 | | |
| | V | 230 |
| | V | 230 |
| Relative negative tolerance / of the control supply voltage / at 60 Hz / for AC | % | -15 |
| Relative positive tolerance / of the control supply voltage / at 60 Hz / for AC | % | 10 |
| Type of display / for fault signal | | red |
| |
| Mechanical design: |
| Size of the engine control device | | S12 |
| Width | mm | 160 |
| Height | mm | 230 |
| Depth | mm | 278 |
| Type of mounting | | screw fixing |
| Built in orientation | | With additional fan: With vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back Without additional fan: With vertical mounting surface +/-10° rotatable, with vertical mounting surface +/- 10° t |
| Distance, to be maintained, to the ranks assembly | | |
| | mm | 100 |
| | mm | 5 |
| | mm | 75 |
| Altitude of installation site / at a height over sea level | m | 5,000 |
| Cable length / maximum | m | 300 |
| Number of poles / for main current circuit | | 3 |
| |
| Electrical connections: |
| Design of the electrical connection | | |
| | | busbar connection |
- for auxiliary and control current circuit
| | spring-loaded terminals |
| Number of NC contacts / for auxiliary contacts | | 0 |
| Number of NO contacts / for auxiliary contacts | | 2 |
| Number of change-over switches / for auxiliary contacts | | 1 |
| Type of the connectable conductor cross-section / for main contacts / for box terminal / when using the front clamping point | | |
- finely stranded / with conductor end processing
| | 70 ... 240 mm² |
- finely stranded / without conductor end processing
| | 70 ... 240 mm² |
| | | 95 ... 300 mm² |
| Type of the connectable conductor cross-section / for main contacts / for box terminal / when using the back clamping point | | |
- finely stranded / with conductor end processing
| | 120 ... 185 mm² |
- without conductor final cutting / without conductor end processing
| | 120 ... 185 mm² |
| | | 120 ... 240 mm² |
|