| SIRIUS SOFT STARTER, S12, 205 A, 200 HP/575 V, 50 DEG., 400-600 V AC, 115 V AC, CAGE CLAMP TERMINALS |
|
General details: |
product brand name | | SIRIUS |
Product equipment | | |
- integrated bridging contact system
| | Yes |
| | Yes |
Product function | | |
- intrinsic device protection
| | Yes |
- motor overload protection
| | Yes |
- evaluation of thermal resistor motor protection
| | No |
| | Yes |
- adjustable current limitation
| | Yes |
| | No |
Product component / outlet for enine brake | | No |
Item designation | | |
- according to DIN EN 61346-2
| | Q |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | G |
|
Power Electronics: |
product designation | | soft starters for standard applications |
Operating current | | |
| A | 230 |
| A | 205 |
| A | 180 |
Emitted mechanical power / for three-phase servomotors | | |
- at 400 V / at standard switching / at 40 °C
| | |
| W | 132,000 |
- at 500 V / at standard switching / at 40 °C
| | |
| W | 160,000 |
Operating frequency | | |
| Hz | 50… 60 |
Relative negative tolerance / of the operating frequency | % | -10 |
Relative positive tolerance / of the operating frequency | % | 10 |
Operating voltage / with standard circuit / rated value | V | 400… 600 |
Relative negative tolerance / of the operating voltage / with standard circuit | % | -15 |
Relative positive tolerance / of the operating voltage / with standard circuit | % | 10 |
Minimum load in % of l_M | % | 20 |
Adjustable rated current / of the motor / for motor overload protection / minimum | A | 130 |
Continuous operating current in % of l_e / at 40°C | % | 115 |
Active power loss / at operating current / at 40°C / during operating phase / typical | W | 90 |
|
Control electronics: |
Type of voltage / of the controlled supply voltage | | AC |
Control supply voltage frequency / 1 / rated value | Hz | 50 |
Control supply voltage frequency / 2 / rated value | Hz | 60 |
Relative negative tolerance / of the control supply voltage frequency | % | -10 |
Relative positive tolerance / of the control supply voltage frequency | % | 10 |
Control supply voltage / 1 | | |
| V | 115 |
| V | 115 |
Relative negative tolerance / of the control supply voltage / at 60 Hz / for AC | % | -15 |
Relative positive tolerance / of the control supply voltage / at 60 Hz / for AC | % | 10 |
Type of display / for fault signal | | red |
|
Mechanical design: |
Size of the engine control device | | S12 |
Width | mm | 160 |
Height | mm | 230 |
Depth | mm | 278 |
Type of mounting | | screw fixing |
Built in orientation | | With additional fan: With vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back Without additional fan: With vertical mounting surface +/-10° rotatable, with vertical mounting surface +/- 10° t |
Distance, to be maintained, to the ranks assembly | | |
| mm | 100 |
| mm | 5 |
| mm | 75 |
Altitude of installation site / at a height over sea level | m | 5,000 |
Cable length / maximum | m | 300 |
Number of poles / for main current circuit | | 3 |
|
Electrical connections: |
Design of the electrical connection | | |
| | busbar connection |
- for auxiliary and control current circuit
| | spring-loaded terminals |
Number of NC contacts / for auxiliary contacts | | 0 |
Number of NO contacts / for auxiliary contacts | | 2 |
Number of change-over switches / for auxiliary contacts | | 1 |
Type of the connectable conductor cross-section / for main contacts / for box terminal / when using the front clamping point | | |
- finely stranded / with conductor end processing
| | 70 ... 240 mm² |
- finely stranded / without conductor end processing
| | 70 ... 240 mm² |
| | 95 ... 300 mm² |
Type of the connectable conductor cross-section / for main contacts / for box terminal / when using the back clamping point | | |
- finely stranded / with conductor end processing
| | 120 ... 185 mm² |
- without conductor final cutting / without conductor end processing
| | 120 ... 185 mm² |
| | 120 ... 240 mm² |
|