| | CIRCUIT-BREAKER SZ S00, FOR MOTOR PROTECTION, CLASS 10, A-RELEASE 2.8...4A, N-RELEASE 52A, SPRING-L. CONNECTION, STANDARD SW. CAPACITY W. TRANSVERSE AUX. SWITCH 1NO+1NC |
| |
| General technical data: |
| product brand name | | SIRIUS |
| product designation | | 3RV2 circuit breaker |
| Size of the circuit-breaker | | S00 |
| Trip class | | CLASS 10 |
| Protection class IP / on the front | | IP20 |
| Degree of pollution | | 3 |
| Installation altitude / at a height over sea level / maximum | m | 2,000 |
| Ambient temperature | | |
| | °C | -50… +80 |
| | °C | -20… +60 |
| | °C | -50… +80 |
| Resistance against shock | | 25g / 11 ms |
| Impulse voltage resistance / rated value | kV | 6 |
| Insulation voltage / rated value | V | 690 |
| Active power loss / total / typical | W | 6.3 |
| Item designation | | |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | F |
- according to DIN EN 61346-2
| | F |
| Mechanical operating cycles as operating time | | |
- of the main contacts / typical
| | 100,000 |
- of the auxiliary contacts / typical
| | 100,000 |
| Design of the auxiliary switch | | transverse |
| Type of the driving mechanism / motor drive | | No |
| Design of the operating mechanism | | selector switch |
| Product function | | |
| | | Yes |
- phase disturbance recognition
| | Yes |
| Product component | | |
| | | Yes |
- undervoltage release mechanism
| | No |
| | | No |
| Product extension / optional / motor drive | | No |
| |
| Main circuit: |
| Number of poles / for main current circuit | | 3 |
| Operating voltage / at AC-3 / rated value / maximum | V | 690 |
| Operating current / at AC-3 / at 400 V / rated value | A | 3.6 |
| Service power / at AC-3 | | |
| | W | 1,500 |
| | W | 2,200 |
| | W | 3,000 |
| Frequency of operation / at AC-3 / according to IEC 60947-6-2 / maximum | 1/h | 15 |
| Arrangement of electrical connectors / for main current circuit | | Top and bottom |
| Adjustable response current | | |
- of the non-delayed short-circuit release
| A | 52… 52 |
- of the current-dependent overload release
| A | 2.8… 4 |
| Service power / at AC-3 / at 230 V / rated value | W | 750 |
| Continuous current / rated value | A | 4 |
| |
| Auxiliary circuit: |
| Product extension / auxiliary switch | | Yes |
| Number of NC contacts / for auxiliary contacts / instantaneous switching | | 1 |
| Number of NO contacts / for auxiliary contacts / instantaneous switching | | 1 |
| Number of change-over switches / for auxiliary contacts | | 0 |
| Operating current / of the auxiliary contacts | | |
| | A | 2.5 |
| | | |
| | A | 2 |
| | A | 0.5 |
| | | |
| | A | 1 |
| | A | 1 |
| | A | 0.15 |
| |
| Inputs/ Outputs: |
| Number of digital inputs | | 0 |
| |
| Short-circuit: |
| Breaking capacity limit short-circuit current (lcu) | | |
| | A | 100,000 |
| | A | 100,000 |
| | A | 6,000 |
| Design of the fuse link / for short-circuit protection of the auxiliary switch / required | | Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A) |
| Design of the overcurrent release and short-circuit release | | thermomagnetic |
| |
| Installation/mounting/dimensions: |
| Built in orientation | | any |
| Type of mounting | | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715 |
| Width | mm | 45 |
| Height | mm | 109 |
| Depth | mm | 91 |
| Distance, to be maintained, to the ranks assembly | | |
| | mm | 0 |
| | mm | 0 |
| | mm | 50 |
| | mm | 50 |
| | mm | 0 |
| Distance, to be maintained, to earthed part | | |
| | mm | 0 |
| | mm | Назад в раздел
|