| | TIME RELAY, SOLID-STATE, OFF-DELAY, 2 CO CONTACTS, W/O AUX. VOLTAGE, 7 DELAY RANGES 0.05...100S, DC 50V, W. LED, SCREW CONNECTION |
| |
| General technical details: |
| product brand name | | SIRIUS |
| product designation | | timing relay |
| Protection class IP / on the front | | IP40 |
| Protection class IP / of the terminal | | IP20 |
| Built in orientation | | any |
| Supply voltage frequency | | |
- 1 / for auxiliary and control current circuit
| | |
| | Hz | 50 |
| | Hz | 60 |
| Installation altitude / at a height over sea level / maximum | m | 2,000 |
| Ambient temperature | | |
| | °C | -40… +85 |
| | °C | -40… +85 |
| Relative humidity | | |
| | % | 15… 70 |
| Conductor-bound parasitic coupling BURST / according to IEC 61000-4-4 | | 2 kV network connection / 1 kV control connection |
| Conductor-bound parasitic coupling conductor-earth SURGE / according to IEC 61000-4-5 | | 2 kV |
| Conductor-bound parasitic coupling conductor-conductor SURGE / according to IEC 61000-4-5 | | 1 kV |
| Electrostatic discharge / according to IEC 61000-4-2 | | 4 kV contact discharge / 8 kV air discharge |
| Field-bound parasitic coupling / according to IEC 61000-4-3 | | 10 V/m |
| Resistance against vibration | | 10 ... 55 Hz / 0.35 mm |
| Impulse voltage resistance / rated value | V | 4,000 |
| Insulation voltage / rated value | V | 300 |
| Active power loss / total / typical | W | 2 |
| Item designation / according to DIN 40719 extendable after IEC 204-2 / according to IEC 750 | | K |
| Item designation / according to DIN EN 61346-2 | | K |
| Category / according to EN 954-1 | | none |
| Protection against electrical shock | | finger-safe |
| |
| |
| General details: |
| Control supply voltage frequency | | |
| | Hz | 50… 60 |
| Working range factor supply voltage rated value | | |
| | | |
| | | 0.85… 1.1 |
| | | |
| | | 0.85… 1.1 |
| | | 0.85… 1.1 |
| |
| Auxiliary circuit: | | |
| Operating current / of auxiliary contacts | | |
- as normally closed contact / for AC-15
| | |
| | A | 3 |
| | A | 3 |
- as normally open contact / for AC-15
| | |
| | A | 3 |
| | A | 3 |
| | | |
| | A | 3 |
| | | |
| | A | 1 |
| | A | 0.2 |
| | A | 0.1 |
| Number of NC contacts / delayed switching | | 0 |
| Number of NC contacts / non-delayed | | 0 |
| |
| Short-circuit: | | |
| Design of the fuse link / for short-circuit protection of the auxiliary switch / required | | fuse gL/gG: 4 A |
| Type of mounting | | screw and snap-on mounting onto 35 mm standard mounting rail |
| |
| Installation/mounting/dimensions: |
| Width | mm | 22.5 |
| Height | mm | 102 |
| Depth | mm | 91 |
| Distance, to be maintained, to the ranks assembly | | |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| Distance, to be maintained, to earthed part | | |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| Distance, to be maintained, conductive elements | | |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| |
| Connections: | | |
| Design of the snap-on socket base | | none |
| Design of the electrical connection | | |
| | | No |
- for auxiliary and control current circuit
| | screw
|