| | AS-INTERFACE COMPACT MOD. K45, IP67, DIGITAL, 2 IN-/OUTPUTS, 2X1 INPUT, 200MA MAX., PNP, 2 X 1OUTP., ELECTR.,1.5A,DC 24V 3A MAX. FOR ALL OUTPUTS 4 X M12-SOCKETS |
| |
| General technical data: |
| Design of the product | | digital I/O modules for operation in the field, IP67 - K45 |
| Type | | 2 inputs / 2 outputs |
| Design of the slave type | | standard slave |
| I/O configuration | | 3 |
| ID/ID2 code | | 0/F |
| Number / I/O sockets | | 4 |
| Design of the electrical connection / of the inputs and outputs | | M12 screw-type terminals |
| AS interface / total current input / max | mA | 270 |
| operating voltage | | |
- according to AS-Interface spezification
| V | 26.5… 31.6 |
| Ground terminal | | Using PIN5 on the M12 sockets. Outgoing via flat tab sleeve (2.8 x 0.8 mm form A) |
| Addressing | | front addressing socket |
| AS interface / Connection / Polarity reversal protection | | built-in |
| Delivery note | | the modules are delivered without mounting plate |
| Note 1 | | All K45 compact modules are delivered with stainless steel screws/sockets |
| Note 2 | | An external additional supply (AUX POWER) of 20 to 30 V DC is required for the supply of the output circuits. The additional supply must comply with VDE 0106 (PELV), protection class III. |
| |
| Sensor supply: |
| Type of voltage supply / for the sensor supply | | using AS-Interface |
| Input voltage | V | 20… 30 |
| Characteristic feature of the sensor supply / short-circuit and overload resistant | | Yes |
| Current carrying capacity / of the sensor supply / for all inputs | | |
- at ambient temperature 40 °C
| mA | 200 |
| |
| Inputs: |
| Number of digital inputs | | 2 |
| type of the connection technology | | 2-conductor and 3-conductor technology |
| Input circuit | | PNP transistor |
| Type of voltage / of the input voltage | | DC |
| Inputs / switching level High / min | V | 10 |
| Input current / at the digital input | | |
| | mA | 6 |
| | mA | 1.5 |
| Inputs | | |
- sensor supply using AS-Interface
| | short-circuit and overload resistant |
| Inputs / socket assignment | | |
| | | sensor supply L+ |
| | | data input |
| | | sensor supply L- |
| | | data input |
| | | ground terminal |
| Design of the pin assignment / of the inputs | | standard assignement |
| |
| Outputs: |
| Number of digital outputs | | 2 |
| Type of voltage / of the outputs | | DC |
| Outputs / external power supply 24 V DC | | using black AS-Interface flat cable |
| Output current / at the digital output / for signal <1> / nominal value | A | 2 |
| Outputs / aggregate current | | |
| | A | 3 |
| Design of the switching output | | PNP transistor |
| Design of the pin assignment / of the outputs | | standard assignement |
| Outputs / socket assignment | | 3 = "-", 4 = output, 5 = ground terminal |
| Characteristic feature of the output / short-circuit protected | | Yes |
| Outputs | | |
| | | built-in |
| | | built-in |
| | | built-in |
| |
| Status display |
| | | yellow LED |
| | | green LED |
- display of AS-Interface/diagnostics
| | green/red dual LED |
| |
| Assignment of data bits |
| | | PIN 4/2 = IN1 (D0) |
| | | PIN 4/2 = IN2 (D1) |
| | | PIN 4 = OUT3 (D2) |
| | | PIN 4 = OUT4 (D3) |
| |
| Ambient conditions: |
| |
| Ambient temperature | | |
| | °C | -25… +85 |
| | °C | -40… +85 |
| Protection class IP | | IP67 |
| |
| Mechanical design: |
| Width | mm | 45 |
| Height | mm | 80 |
| Depth | mm | 30 |
| Type of mounting | | standard rail mounting/wall mounting using mounting plate for K45 compact module |
| |
| Certificates/approvals: |
| AS-Interface certificate | | yes |
| Approvals | | UL, CSA, shipbuilding |
| General Product Approval | Test Certificates | | | |
| | |
| | |
| |
| last change: | Mar 8, 2012 |