| | SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 4SI SIRIUS, 4 POINT-TO-POINT INTERFACES 15MM WIDTH, IO-LINK MASTER FOR SIRIUS SWITCHGEAR |
| |
| General technical data: |
| product brand name | | SIRIUS |
| product designation | | ET200S interface module for SIRIUS controls with IO-Link |
| Protection class IP | | IP20 |
| Degree of pollution | | 2 according to IEC 61131 |
| Insulation voltage / rated value | V | 500 |
| Installation altitude / at a height over sea level / maximum | m | 2,000 |
| Ambient temperature | | |
| | °C | -40… +70 |
- with vertical mounting position
| | |
| | °C | 0… 50 |
- with horizontal mounting position
| | |
| | °C | 0… 60 |
| | °C | -40… +70 |
| Relative humidity | | |
| | % | 15… 95 |
| Conductor-bound parasitic coupling BURST | | |
- according to IEC 61000-4-4
| | 2 kV |
| Conductor-bound parasitic coupling conductor-earth SURGE | | |
- according to IEC 61000-4-5
| | 2 kV |
| Conductor-bound parasitic coupling conductor-conductor SURGE | | |
- according to IEC 61000-4-5
| | 1 kV |
| Electrostatic discharge / according to IEC 61000-4-2 | | 4 kV contact discharge / 8 kV air discharge |
| Field-bound parasitic coupling / according to IEC 61000-4-3 | | 10 V/m |
| Resistance against shock | | 15g / 11 ms |
| Resistance against vibration | | 0.35 mm / 5g |
| |
| Communication: |
| Protocol / will be supported / IO-Link protocol | | Yes |
| IO-Link transfer rate | | COM2 (38,4 kBaud) |
| Operation mode at input/ output link | | IO-Link, deactivated |
| Design of the electrical connection | | Connection using terminal module |
| Data volume | | |
- of the address range of the inputs / with cyclical transfer
| | |
- per IO-Link port / maximum
| byte | 8 |
| | byte | 32 |
- of the address range of the outputs / with cyclical transfer
| | |
- per IO-Link port / maximum
| byte | 8 |
- for all IO-Link ports / maximum
| byte | 32 |
| Number of IO-Link ports | | 4 |
| Design of cable | | unshielded |
| Point-to-point cycle time | | |
- between master and IO-Link device / minimum
| ms | 5 |
- between the master and the backplane bus / minimum
| ms | 5 |
| Type of IO-Link device / connectable | | SIRIUS switching technology |
| Product function | | |
| | | Yes |
| | | No |
| | | Yes |
| Galvanic isolation | | |
| | | No |
- between the ports and the backplane bus
| | Yes |
| Type of voltage | | |
| | | DC |
| Supply voltage / 1 / for DC | | |
| | V | 24 |
| Consumed current / for rated value of the supply voltage | | |
| | A | 0.3 |
| Active power loss / total / typical | W | 1 |
| |
| Short-circuit: |
| Short-circuit firmness | | 0.4 A per port |
| |
| Installation/mounting/dimensions: |
| Built in orientation | | any |
| Type of mounting | | clip-on |
| Width | mm | 15 |
| |
| Certificates/approvals: |
| Verification of suitability | | CE / UL / CSA |
| Verification of suitability / for gas explosion protection for zone 1/2 | | zone 2 |
| General Product Approval | other | | ROSTEST | Manufacturer | | | | | |
| |
| Further information: |
| Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/industrial-controls/catalogs |
| Industry Mall (Online ordering system) http://www.siemens.com/industrial-controls/mall |
| CAx-Online-Generator http://www.siemens.com/cax |
| Service&Support (Manuals, Certificates, Characteristics, FAQs,...) http://support.automation.siemens.com/WW/view/en/3RK1005-0LB00-0AA0/all |
| Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...) http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3RK1005-0LB00-0AA0 |
| |
| |
| | |
| |
| last change: | Feb 6, 2012 |