| General technical data: |
| Product brand name | | SIRIUS |
| Product designation | | contactor relay |
| Size of the contactor | | S00 |
| Protection class IP / on the front | | IP20 |
| Degree of pollution | | 3 |
| Insulation voltage / with degree of pollution 3 / rated value | V | 690 |
| Installation altitude / at a height over sea level / maximum | m | 2,000 |
| Ambient temperature | | |
| | °C | -55… 80 |
| | °C | -55… 80 |
| | °C | -25… 60 |
| Resistance against shock | | 10g / 5 ms and 5g / 10 ms |
| Impulse voltage resistance / rated value | kV | 6 |
| Item designation | | |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | K |
- according to DIN EN 61346-2
| | K |
| Mechanical operating cycles as operating time | | |
- of the contactor / typical
| | 10,000,000 |
| |
| Control circuit: |
| Type of voltage / of the controlled supply voltage | | AC |
| Control supply voltage frequency | | |
| | Hz | 50 |
| | Hz | 60 |
| Control supply voltage / 1 | | |
- at 50 Hz / for AC / rated value
| V | 230 |
- at 60 Hz / for AC / rated value
| V | 230 |
| Operating range factor control supply voltage rated value / of the solenoid | | |
| | | 0.8… 1.1 |
| | | 0.85… 1.1 |
| Apparent pull-in power / of the solenoid / for AC | V·A | 37 |
| Apparent holding power / of the solenoid / for AC | V·A | 5.7 |
| Inductive power factor | | |
- with the pull-in power of the coil
| | 0.8 |
- with the pull-in power of the coil
| | 0.25 |
| |
| Auxiliary circuit: |
| Product extension / auxiliary switch | | No |
| Identification number and letter for switching elements | | 44 E |
| Contact reliability / of the auxiliary contacts | | 1 faulty switching per 100 million (17 V, 1 mA) |
| Number of NC contacts / for auxiliary contacts | | 4 |
| | | 4 |
| | | 0 |
| | | 0 |
| | | 0 |
| Number of NO contacts / for auxiliary contacts | | 4 |
| | | 4 |
| | | 0 |
| | | 0 |
| | | 0 |
| Number of changeover contacts | | |
| | | 0 |
| Operating current / of the auxiliary contacts | | |
| | A | 10 |
| | | |
| | A | 10 |
| | A | 3 |
| | A | 2 |
| | A | 1 |
| | | |
| | | |
| | A | 6 |
| | A | 3 |
| | A | 1 |
| | | |
| | A | 6 |
| | A | 1 |
| | A | 0.3 |
| |
| Short-circuit: |
| Design of the fuse link / for short-circuit protection of the auxiliary switch | | |
| | | Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A) |
| |
| Installation/mounting/dimensions: |
| Built in orientation | | vertical |
| Type of mounting | | screw and snap-on mounting onto 35 mm standard mounting rail |
| Width | mm | 45 |
| Height | mm | 70 |
| Depth | mm | 73 |
| Distance, to be maintained, to the ranks assembly | | |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| Distance, to be maintained, to earthed part | | |
| | mm | 6 |
| | mm | 0 |
| | mm | 6 |
| | mm | Назад в раздел
|