| | SEMI-COND. CONTACTOR 3RF2,1-PH. AC 51 90 A 40 DEGREES C 48-600 V / 110-230 V AC RING TERMINAL |
| |
| General technical data: |
| Product brand name | | SIRIUS |
| product designation | | solid-state contactor |
| Product function | | zero-point switching |
| Number of poles / for main current circuit | | 1 |
| Protection class IP | | IP20 |
| Product designation / _1 / of the accessories that can be ordered | | terminal cover |
| Manufacturer article number / _1 / of the accessories that can be ordered | | 3RF2900-3PA88 |
| Product designation / _4 / of the accessories that can be ordered | | load monitoring |
| Manufacturer article number / _4 / of the accessories that can be ordered | | 3RF2990-0GA36 |
| Ambient temperature | | |
| | °C | -25… 60 |
| | °C | -55… 80 |
| Installation altitude / at a height over sea level / maximum | m | 1,000 |
| Resistance against vibration / according to IEC 60068-2-6 | | 2g |
| Resistance against shock / according to IEC 60068-2-27 | | 15g / 11 ms |
| Item designation | | |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | K |
- according to DIN EN 61346-2
| | Q |
| Number of NC contacts / for auxiliary contacts | | 0 |
| Number of NO contacts / for auxiliary contacts | | 0 |
| Number of change-over switches / for auxiliary contacts | | 0 |
| |
| Main circuit: |
| Number of NO contacts / for main contacts | | 1 |
| Number of NC contacts / for main contacts | | 0 |
| Operating current | | |
- at AC-1 / at 400 V / rated value
| A | 88 |
| | A | 88 |
| Operating current / minimum | mA | 500 |
| Operating voltage | | |
- at 50 Hz / at AC / rated value
| V | 48… 600 |
- at 60 Hz / at AC / rated value
| V | 48… 600 |
| Working area related to the operating voltage | | |
| | V | 40… 660 |
| | V | 40… 660 |
| Operating frequency | | |
| | Hz | 50… 60 |
| Relative symmetrical tolerance / of the operation frequency | % | 10 |
| Insulation voltage / rated value | V | 600 |
| Voltage slew rate / at the thyristor / for main contacts / maximum permissible | V/µs | 1,000 |
| Block voltage / at the thyristor / for main contacts / maximum permissible | V | 1,600 |
| Reverse current / of the thyristor | mA | 10 |
| Derating temperature | °C | 40 |
| Active power loss / total / typical | W | 117 |
| Resistance against the impulse current / rated value | A | 1,150 |
| I2t-level / maximum | A?·s | 6,600 |
| |
| Control circuit: |
| Control supply voltage frequency | | |
| | Hz | 50 |
| | Hz | 60 |
| Type of voltage / of the controlled supply voltage | | AC |
| Control supply voltage / 1 | | |
| | | |
| | V | 110 |
| | V | 230 |
| | | |
| | V | 110 |
| | V | 230 |
| Control supply voltage | | |
- at 50 Hz / for AC / final value for signal<0>-recognition
| V | 40 |
- at 60 Hz / for AC / final value for signal<0>-recognition
| V | 40 |
| Tolerance of the line frequency | Hz | 5 |
| Relative symmetrical tolerance / of the supply voltage frequency | % | 10 |
| Control current | | |
- at minimum control supply voltage / for AC
| mA | 2 |
| | mA | 15 |
| Fuse assignments | | https://www.automation.siemens.com/cd-static/material/info/3RF21_eng.pdf |
| |
| Installation/mounting/dimensions: |
| Type of mounting | | screw fixing |
| Type of fixing/fixation / series installation | | Yes |
| Design of the thread / of the screw for fastening of the operating resource | | M4 |
| Tightening torque / of the screw for fastening of the operating resource | N·m | 1.5 |
| Width | mm | 180 |
| Height | mm | 100 |
| Depth | mm | 162.5 |
| |
| Connections: |
| Design of the electrical connection / for main current circuit | | ring cable connection |
| Design of the thread / of the connection screw / for main contacts | | M5 |
| Tightening torque / for main contacts | | |
- with screw-type terminals
| N·m | 2… 2.5 |
| Type of the connectable conductor cross-section | | |
- for main contacts / for JIS cable lug
| | JIS C 2805 R 2-5, 5,5-5, 8-5, 14-5 |
- for DIN cable lug / for main contacts
| | DIN 46234 -5-2,5, -5-6, -5-10, -5-16, -5-25 |
| | | |
- for auxiliary and control contacts
| | 1x (AWG 20 ... 12) |
- for auxiliary and control contacts
| | |
| | | Назад в раздел
|