3RB3123-4QB0 - OVERLOAD RELAY 6...25 A FOR MOTOR PROTECTION SIZE S0, CLASS 5...30 CONTACTOR ASS. MAIN CIRCUIT: SCREW CONN. AUX.CIRCUIT: SCREW CONN. MANUAL-AUTOM.-RESET INT. GROUND FAULT DETECTION (siemens) - Quad Industry GmbH

Артикул: 3RB3123-4QB0
Наименование: OVERLOAD RELAY 6...25 A FOR MOTOR PROTECTION SIZE S0, CLASS 5...30 CONTACTOR ASS. MAIN CIRCUIT: SCREW CONN. AUX.CIRCUIT: SCREW CONN. MANUAL-AUTOM.-RESET INT. GROUND FAULT DETECTION (siemens)
Производитель: Siemens


Наименование продукта
OVERLOAD RELAY 6...25 A FOR MOTOR PROTECTION SIZE S0, CLASS 5...30 CONTACTOR ASS. MAIN CIRCUIT: SCREW CONN. AUX.CIRCUIT: SCREW CONN. MANUAL-AUTOM.-RESET INT. GROUND FAULT DETECTION
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2009-11-19
OVERLOAD RELAY 6...25 A FOR MOTOR PROTECTION SIZE S0, CLASS 5...30 CONTACTOR ASS. MAIN CIRCUIT: SCREW CONN. AUX.CIRCUIT: SCREW CONN. MANUAL-AUTOM.-RESET INT. GROUND FAULT DETECTION
 
General technical data:
product brand name   SIRIUS
product designation   solid-state overload relay
Protection class IP / on the front   IP20
Insulation voltage / with degree of pollution 3 / rated value V 690
Installation altitude / at a height over sea level / maximum m 2,000
Ambient temperature    
  • during storage
°C -40 +80
  • during transport
°C -40 +80
  • during operating
°C -25 +60
Relative humidity    
  • during operating phase
/ % 95
EMC immunity to interference    
  • according to IEC 60947-1
  corresponds to degree of severity 3
EMC emitted interference    
  • according to IEC 60947-1
  CISPR 11, environment B (residential area)
Conductor-bound parasitic coupling BURST    
  • according to IEC 61000-4-4
  2 kV (power ports), 1 kV (signal ports) corresponds to degree of severity 3
Conductor-bound parasitic coupling conductor-earth SURGE    
  • according to IEC 61000-4-5
  2 kV (line to earth) corresponds to degree of severity 3
Conductor-bound parasitic coupling conductor-conductor SURGE    
  • according to IEC 61000-4-5
  1 kV (line to line) corresponds to degree of severity 3
Electrostatic discharge    
  • according to IEC 61000-4-2
  6 kV contact discharge / 8 kV air discharge
Field-bound parasitic coupling    
  • according to IEC 61000-4-3
  10 V/m
Resistance against shock   15g / 11 ms
Impulse voltage resistance / rated value kV 6
Active power loss / total / typical W 0.1
Item designation    
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  F
  • according to DIN EN 61346-2
  F
Size of overload relay   S0
Size of the contactor / can be combined / company-specific   S0
type of protection   PTB 09 ATEX 3001 Ex II (2) GD
Type of assignement   2
Trip class   CLASS 5, 10, 20 and 30 adjustable
 
Main circuit:
Number of poles / for main current circuit   3
Operating voltage / at AC-3 / rated value    
  • maximum
V 690
Operating current / at AC-3 / at 400 V    
  • rated value
A 25
Adjustable response current    
  • of the current-dependent overload release
A 6 25
Service power / for three-phase servomotors / at 400 V / at 50 Hz    
  • for AC three-phase
kW 3 11
Operating current / of the fuse link    
  • rated value
A 50
 
Auxiliary circuit:
Contact reliability / of the auxiliary contacts   acceptability for PLC control (17 V, 5 mA)
Number of NC contacts / for auxiliary contacts   1
Number of NO contacts / for auxiliary contacts   1
Number of change-over switches / for auxiliary contacts   0
Operating current / of the auxiliary contacts    
  • at AC-15
   
  • at 24 V
A 4
  • at 110 V
A 4
  • at 120 V
A 4
  • at 125 V
A 4
  • at 230 V
A 3
  • at DC-13
   
  • at 24 V
A 2
  • at 60 V
A 1
  • at 110 V
A 0.3
  • at 125 V
A 0.3
  • at 220 V
A 1
 
Short-circuit:
Design of the fuse link / for short-circuit protection of the auxiliary switch / required   fuse gL/gG: 6 A
 
Installation/mounting/dimensions:
Built in orientation   any
Type of mounting   direct mounting
Width mm 45
Height mm 69.7
Depth mm 83.5
Distance, to be maintained, to the ranks assembly    
  • forwards
mm 0
  • backwards
mm 0
  • upwards
mm 0
  • downwards
mm 0
  • sidewards
mm 0
Distance, to be maintained, to earthed part    
  • forwards
mm 6
  • backwards
mm 0
  • upwards
mm 6
  • downwards
mm 6
  • sidewards
mm 6
Distance, to be maintained, conductive elements  Назад в раздел