| PROCESSING UNIT FOR FULL MOTOR PROTECTION (MONOSTABLE) FOR IO-LINK SIZE S00...S12, CLASS 5...30 STAND-ALONE INSTALLATION MAIN CIRCUIT: -- AUX. CIRCUIT: SCREW CONNECTION MANUAL-AUTOMATIC-RESET |
|
General technical data: |
product brand name | | SIRIUS |
product designation | | solid-state overload relay |
Protection class IP / on the front | | IP20 |
Insulation voltage / with degree of pollution 3 / rated value | V | 300 |
Installation altitude / at a height over sea level / maximum | m | 2,000 |
Ambient temperature | | |
| °C | -40… +80 |
| °C | -40… +80 |
| °C | -25… +60 |
Relative humidity | | |
| / % | 100 |
EMC immunity to interference | | |
| | corresponds to degree of severity 3 |
Conductor-bound parasitic coupling BURST | | |
- according to IEC 61000-4-4
| | 2 kV (power ports), 1 kV (signal ports) corresponds to degree of severity 3 |
Conductor-bound parasitic coupling conductor-earth SURGE | | |
- according to IEC 61000-4-5
| | 2 kV (line to earth) corresponds to degree of severity 3 |
Conductor-bound parasitic coupling conductor-conductor SURGE | | |
- according to IEC 61000-4-5
| | 1 kV (line to line) corresponds to degree of severity 3 |
Electrostatic discharge | | |
- according to IEC 61000-4-2
| | 6 kV contact discharge / 8 kV air discharge |
Field-bound parasitic coupling | | |
- according to IEC 61000-4-3
| | 10 V/m |
Resistance against shock | | 15g / 11 ms |
Impulse voltage resistance / rated value | V | 4,000 |
Active power loss / total / typical | W | 0.5 |
Item designation | | |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | F |
- according to DIN EN 61346-2
| | F |
Size of overload relay | | S00 |
Size of the contactor / can be combined / company-specific | | S00 ... S12 |
Trip class | | CLASS 5, 10, 20 and 30 adjustable |
|
Main circuit: |
Adjustable response current | | |
- of the current-dependent overload release
| A | 0.3… 630 |
Operating current / of the fuse link | | |
| A | 6 |
|
Auxiliary circuit: |
Contact reliability / of the auxiliary contacts | | acceptability for PLC control (17 V, 5 mA) |
Number of NC contacts / for auxiliary contacts | | 0 |
Number of NO contacts / for auxiliary contacts | | 1 |
Number of change-over switches / for auxiliary contacts | | 1 |
Operating current / of the auxiliary contacts | | |
| | |
| A | 6 |
| A | 6 |
| A | 3 |
| | |
| A | 2 |
| A | 0.55 |
| A | 0.3 |
| A | 0.2 |
|
Short-circuit: |
Design of the fuse link / for short-circuit protection of the auxiliary switch / required | | fuse gL/gG: 6 A |
|
Installation/mounting/dimensions: |
Built in orientation | | any |
Type of mounting | | stand-alone installation |
Width | mm | 45 |
Height | mm | 111 |
Depth | mm | 95 |
Distance, to be maintained, to the ranks assembly | | |
| mm | 0 |
| mm | 0 |
| mm | 0 |
| mm | 0 |
| mm | 0 |
Distance, to be maintained, to earthed part | | |
| mm | 0 |
| mm | 0 |
| mm | 0 |
| mm | 0 |
| mm | 6 |
Distance, to be maintained, conductive elements | | |
| mm | 0 |
| mm | 0 |
| mm | 0 |
| mm | 0 |
| mm | 6 |
|
Connections: |
Design of the electrical connection | | |
- for auxiliary and control current circuit
| | screw-type terminals |
Product function / removable terminal for auxiliary and control circuit | | Yes |
Type of the connectable conductor cross-section | | |
| | |
| | 1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²) |
| | |
- with conductor end processing