| OVERLOAD RELAY 50...200 A FOR MOTOR PROTECTION SIZE S6, CLASS 10 MOUNT. ONTO CONT./ STAND-ALONE MAIN CIRCUIT: BAR CONNECTION AUX. CIRCUIT: SPRINGLOAD. TERM. MANUAL-AUTOMATIC-RESET |
| |
| General technical details: |
| Product brand name | | SIRIUS |
| product designation | | solid-state overload relay |
| Protection class IP / on the front | | IP20 |
| Insulation voltage / with degree of pollution 3 / rated value | V | 1,000 |
| Adjustable response current | | |
- of the current-dependent overload release
| A | 50… 200 |
| EMC emitted interference | | degree of severity B according to EN 55011 (CISPR 11) and EN 55022 (CISPR 22) |
| Electrostatic discharge / according to IEC 61000-4-2 | | 6 kV contact discharge / 8 kV air discharge |
| Field-bound parasitic coupling / according to IEC 61000-4-3 | | 10 V/m |
| Conductor-bound parasitic coupling BURST / according to IEC 61000-4-4 | | 2 kV (power ports), 1 kV (signal ports) corresponds to degree of severity 3 |
| Conductor-bound parasitic coupling conductor-earth SURGE | | 2 kV (line to earth) corresponds to degree of severity 3 |
| Conductor-bound parasitic coupling conductor-conductor SURGE | | 1 kV (line to line) corresponds to degree of severity 3 |
| Resistance against shock | | 15g / 11 ms |
| Impulse voltage resistance / rated value | kV | 8 |
| Active power loss / total / typical | W | 0.05 |
| type of protection | | PTB 06 ATEX 3001 Ex II (2) GD |
| Type of assignement | | 2 |
| Trip class | | CLASS 10 |
| Item designation | | |
- according to DIN EN 61346-2
| | F |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | F |
| Protection against electrical shock | | finger-safe with cover |
| |
| Control circuit: |
| Design of the electrical connection / for auxiliary and control current circuit | | spring-loaded terminals |
| |
| Main circuit: |
| Number of poles / for main current circuit | | 3 |
| Operating voltage / at AC-3 / rated value / maximum | V | 1,000 |
| Operating current / of the fuse link | | |
| | A | 315 |
| Service power / for three-phase servomotors | | |
| | kW | 22… 90 |
| Design of the electrical connection / for main current circuit | | busbar connection |
| Service power / for three-phase servomotors / at 400 V / at 50 Hz | | |
| | kW | 22… 90 |
| |
| Auxiliary circuit: |
| Contact reliability / of the auxiliary contacts | | acceptability for PLC control (17 V, 5 mA) |
| Operating current / of the auxiliary contacts | | |
| | | |
| | A | 4 |
| | A | 4 |
| | A | 4 |
| | A | 4 |
| | A | 3 |
| | | |
| | A | 2 |
| | A | 0.55 |
| | A | 0.3 |
| | A | 0.3 |
| | A | 0.11 |
| Number of NC contacts | | 1 |
| Number of NO contacts | | 1 |
| Number of change-over switches | | 0 |
| |
| Short-circuit: | | |
| Design of the fuse link / for short-circuit protection of the auxiliary switch / required | | fuse gL/gG: 6 A |
| |
| Mechanical design: |
| Built in orientation | | any |
| Type of mounting | | direct mounting / stand-alone installation |
| Size of the contactor / can be combined / company-specific | | S6 |
| Size of overload relay | | S6 |
| Width | mm | 120 |
| Height | mm | 119 |
| Depth | mm | 155 |
| Distance, to be maintained, to the ranks assembly | | |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| | mm | 0 |
| Distance, to be maintained, to earthed part | | |
| | mm | 0 |
| | mm | 0 |
| | mm | 6 |
| | mm | 0 |
| | mm | 0 |
| Distance, to be maintained, conductive elements | | |
| | mm | 0 |
| | mm | 0 |
| | mm | 6 |
| | mm | 0 |
| | mm | 0 |
| |
| Ambient conditions: |
| Ambient temperature | | |
| | °C | -25… 60 |
| Ambient temperature | | |
| | °C | -40… 80 |
| Ambient temperature | | |
| | °C | -40…Назад в раздел
|