3RA2120-1JA24-0AP0 - LOAD FEEDER FUSELESS DIRECT START, AC 400V, SZ. S0, 7. . .10A, AC 230V SCREW CONNECTION FOR RAIL MOUNTING, TYPE OF COORD. 2,IQ = 150KA (ALSO ACHIEVES TYPE OF COORDINATION 1) 1NO+1NC (CONTACTOR) (siemens) - Quad Industry GmbH

Артикул: 3RA2120-1JA24-0AP0
Наименование: LOAD FEEDER FUSELESS DIRECT START, AC 400V, SZ. S0, 7. . .10A, AC 230V SCREW CONNECTION FOR RAIL MOUNTING, TYPE OF COORD. 2,IQ = 150KA (ALSO ACHIEVES TYPE OF COORDINATION 1) 1NO+1NC (CONTACTOR) (siemens)
Производитель: Siemens


Наименование продукта
LOAD FEEDER FUSELESS DIRECT START, AC 400V, SZ. S0, 7. . .10A, AC 230V SCREW CONNECTION FOR RAIL MOUNTING, TYPE OF COORD. 2,IQ = 150KA (ALSO ACHIEVES TYPE OF COORDINATION 1) 1NO+1NC (CONTACTOR)
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2009-11-19
    Версия от 2011-01-02
 

LOAD FEEDER FUSELESS DIRECT START, AC 400V, SZ. S0, 7. . .10A, AC 230V SCREW CONNECTION FOR RAIL MOUNTING, TYPE OF COORD. 2,IQ = 50KA (ALSO ACHIEVES TYPE OF COORDINATION 1) 1NO+1NC (CONTACTOR)
 
General technical data:
Product brand name   SIRIUS
Product designation   non-fused load feeders 3RA2
Design of the product   direct starter
Size of the load feeder   S0
Protection class IP / frontal/front side   IP20
Degree of pollution   3
Insulation voltage / rated value V 690
Altitude of installation site / at a height over sea level / maximum m 2,000
Ambient temperature    
  • during transport
°C -55 80
  • during storage
°C -55 80
  • during the operating phase
°C -20 60
Impulse voltage resistance / rated value kV 6
Real loss power / per conductor / typical W 3.5
Item designation    
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  Q
  • according to DIN EN 61346-2
  Q
Type of assignement   2
Mechanical operating cycles as operating time / of the contactor    
  • typical
  10,000,000
Manufacturer article number    
  • of the circuit-breakers included in the scope of supply
  3RV2011-1JA10
  • of the contactor included in the scope of supply
  3RT2024-1AP00
  • of the link module included in the scope of supply
  3RA2921-1AA00
Design of the switching contact   mechanical
Type of the motor protection   bimetal
Adjustable response current    
  • of the current-dependent overload release
A 7 10
 
Communication:
Product function / Bus-communication   No
Protocol / will be supported    
  • AS interface protocol
  No
  • PROFIBUS DP protocol
  No
  • PROFINET
  No
Product extension / function module for communication   No
 
Main circuit:
Number of poles / for main current circuit   3
Number of NC contacts / for main contacts   0
Number of NO contacts / for main contacts   3
Operating voltage / at 3 AC / rated value / maximum V 690
Operating current    
  • at AC-1 / at 400 V / rated value
A 10
  • at AC-2 / at 400 V / rated value
A 8.5
  • at AC-3 / at 400 V / rated value
A 8.5
  • at AC-4 / at 400 V / rated value
A 8.5
Service power    
  • at AC-2 / at 400 V / rated value
W 4,000
  • at AC-3
   
  • at 400 V / rated value
W 4,000
  • at 500 V / rated value
W 5,500
  • at 690 V / rated value
W 7,500
  • at AC-4 / at 400 V / rated value
W 4,000
Off-load operating frequency 1/h 10,000
Switching frequency    
  • at AC-1 / according to IEC 60947-6-2 / maximum
1/h 1,000
  • at AC-2 / according to IEC 60947-6-2 / maximum
1/h 1,000
  • at AC-3 / according to IEC 60947-6-2 / maximum
1/h 1,000
  • at AC-4 / according to IEC 60947-6-2 / maximum
1/h 300
 
Control circuit:
Type of voltage / of the controlled supply voltage   AC
control supply voltage frequency    
  • 1 / rated value
Hz 50
Control supply voltage / 1    
  • at 50 Hz / for AC / rated value
V 230
  • at 60 Hz / for AC / rated value
V 230
Apparent holding power / of the solenoid / for AC V·A 8.5
Power factor inductive / at holding power of the coil   0.25
 
Auxiliary circuit:
Product extension / auxiliary switch   Yes
Number of NC contacts / for auxiliary contact   1
Number of NO contacts / for auxiliary contact   1
Number of change-over switches / for auxiliary contact   0
 
Inputs/ Outputs:
Number of digital inputs   0
 
Short-circuit:
Product function / Short circuit protection   Yes
Design of the short-circuit protection   circuit-breakers
Switch-off capacity limit short-circuit current    
  • at 400 V / rated value
A 100,000
  • at 500 V / rated value
A 42,000
  • at 690 V / rated value
A 4,000
 
Installation/mounting/dimensions:
built in orientation   vertical
Type of fixing/fixation   screw and snap-on mounting onto 35 mm standard mounting rail
Width mm 45
Height mm 193.1
Depth mm 97.1
distance, to be maintained, to the ranks assembly    
  • forwards
mm 10
  • backwards
mm 0
  • upwards
mm

Назад в раздел