| | CONTACTOR COMBINATION, STAR-DELTA (FACTORY-ASSEMBLED) WITH FRONT SIDE TIMING RELAY, AC-3 22/30 KW/400 V, 3-POLE, SIZE S2, S2, S0, EL. LOCKED, SCREW CONNECTION, 1 NO, 400 V AC, 50 HZ, |
| |
| General details: |
| product brand name | | SIRIUS |
| product designation | | contactor assembly |
| Degree of pollution | | 3 |
| Insulation voltage / with degree of pollution 3 / rated value | V | 690 |
| Installation altitude / at a height over sea level / maximum | m | 2,000 |
| Ambient temperature | | |
| | °C | -55… +80 |
| | °C | -55… +80 |
| Mechanical operating cycles as operating time | | |
- of the main contacts / typical
| | 10,000,000 |
- of the auxiliary contacts / typical
| | 10,000,000 |
- of the contactor with added auxiliary switch block / typical
| | 10,000,000 |
| |
| Main circuit: |
| Number of poles / for main current circuit | | 3 |
| Number of NC contacts / for main contacts | | 0 |
| Operating voltage / at AC-3 / rated value / maximum | V | 690 |
| |
| Steuerstromkreis/Ansteuerung: |
| Design of activation | | conventional |
| Design of the surge suppressor | | without |
| Working range factor supply voltage rated value / of the magnet coil | | |
| | | |
| | | 0.8… 1.1 |
| | | |
| | | 0.85… 1.1 |
| | | 0.8… 1.1 |
| |
| Auxiliary circuit: |
| Product extension / auxiliary switch | | Yes |
| Number of NC contacts / for auxiliary contacts | | |
| | | 0 |
| Number of NO contacts / for auxiliary contacts | | |
| | | 0 |
| |
| Short-circuit: | | |
| Design of the fuse link | | |
- for short-circuit protection of the auxiliary switch / required
| | fuse gL/gG: 10 A |
- for short-circuit protection of the main circuit
| | |
- with type of assignment 1 / required
| | fuse gL/gG: 125 A |
- at type of coordination 2 / required
| | fuse gL/gG: 63 A |
| |
| Einbau/Befestigung/Abmessung: | | |
| Built in orientation | | with vertical mounting surface +/-180° rotatable, with vertical mounting surface +/- 30° tiltable to the front and back |
| Distance, to be maintained, to the ranks assembly / sidewards | mm | 0 |
| Distance, to be maintained, to earthed part / sidewards | mm | 0 |
| Distance, to be maintained, conductive elements | | |
| | mm | 0 |
| |
| |
| Approbationen/ Zertifikate | | |
| Verification of suitability | | CE / UL / CCC / GL / LRS / BV / DNV / RMRS / RINA / PRS / ABS |
| General Product Approval | Shipping Approval | other | | ROSTEST | | |
| |
| Sicherheitstechnische Merkmale | | |
| Contact reliability / of the auxiliary contacts | | 1 faulty switching per 100 million (17 V, 1 mA) |
| |
| Further information: |
| Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/industrial-controls/catalogs |
| Industry Mall (Online ordering system) http://www.siemens.com/industrial-controls/mall |
| CAx-Online-Generator http://www.siemens.com/cax |
| Service&Support (Manuals, Certificates, Characteristics, FAQs,...) http://support.automation.siemens.com/WW/view/en/3RA1434-8XB20-1AV0/all |
| Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...) http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3RA1434-8XB20-1AV0 |
| |
| |
| | |
| |
| last change: | Aug 22, 2011 |