3RA2415-8XE31-1BB4 - STAR-DELTA COMB. WITH I/O-LINK AC3, 5,5KW/400V DC24V, 3-POLE SZ S00, SCREW TERMINAL ELECTR. AND MECH. INTERLOCK 3NO INTEGR. (siemens) - Quad Industry GmbH

Артикул: 3RA2415-8XE31-1BB4
Наименование: STAR-DELTA COMB. WITH I/O-LINK AC3, 5,5KW/400V DC24V, 3-POLE SZ S00, SCREW TERMINAL ELECTR. AND MECH. INTERLOCK 3NO INTEGR. (siemens)
Производитель: Siemens


Наименование продукта
STAR-DELTA COMB. WITH I/O-LINK AC3, 5,5KW/400V DC24V, 3-POLE SZ S00, SCREW TERMINAL ELECTR. AND MECH. INTERLOCK 3NO INTEGR.
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2009-11-23
STAR-DELTA COMB. WITH I/O-LINK AC3, 5,5KW/400V DC24V, 3-POLE SZ S00, SCREW TERMINAL ELECTR. AND MECH. INTERLOCK 3NO INTEGR.
 
General technical data:
product brand name   SIRIUS
product designation   star-delta (wye-delta) contactor assembly 3RA24
Product function   wye-delta motor start-up
Size of the contactor   S00
Protection class IP / on the front   IP20
Degree of pollution   3
Insulation voltage / with degree of pollution 3 / rated value V 690
Installation altitude / at a height over sea level / maximum m 2,000
Ambient temperature    
  • during transport
°C -55 +80
  • during storage
°C -55 +80
  • during operating
°C -25 +60
Resistance against shock   9.8g / 5 ms and 5.9g / 10 ms
Impulse voltage resistance / rated value kV 6
Active power loss / per conductor / typical W 0.4
Item designation    
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  K
  • according to DIN EN 61346-2
  Q
Manufacturer article number    
  • of the function module for communication included in the scope of supply
  3RA2711-1CA00
  • 1 / of the contactor included in the scope of supply
  3RT2015-1BB41-0CC0
  • 2 / of the contactor included in the scope of supply
  3RT2015-1BB41
  • 3 / of the contactor included in the scope of supply
  3RT2015-1BB41
  • of the RS applied assembly kit
  3RA2913-2BB1
Mechanical operating cycles as operating time    
  • of the main contacts / typical
  10,000,000
  • of the auxiliary contacts / typical
  10,000,000
  • of the contactor / typical
  10,000,000
  • of the contactor with added auxiliary switch block / typical
  10,000,000
 
Communication:
Product function    
  • bus-communication
  Yes
  • control circuit interface with IO link
  Yes
Protocol / will be supported / AS interface protocol   No
 
Main circuit:
Number of poles / for main current circuit   3
Number of NC contacts / for main contacts   0
Number of NO contacts / for main contacts   3
Operating voltage / at AC-3 / rated value / maximum V 690
Operating current    
  • at AC-1 / at 400 V
   
  • at 40 °C ambient temperature / rated value
A 18
  • at 60 °C ambient temperature / rated value
A 16
  • at AC-2 / at 400 V / rated value
A 12
  • at AC-3 / at 400 V / rated value
A 12
Service power    
  • at AC-2 / at 400 V / rated value
kW 5.5
  • at AC-3
   
  • at 400 V / rated value
kW 5.5
  • at 500 V / rated value
kW 7.2
  • at 690 V / rated value
kW 9.2
Off-load operating frequency 1/h 15
Frequency of operation    
  • at AC-1 / according to IEC 60947-6-2 / maximum
1/h 1,000
  • at AC-2 / according to IEC 60947-6-2 / maximum
1/h 1,000
  • at AC-3 / according to IEC 60947-6-2 / maximum
1/h 1,000
  • at AC-4 / according to IEC 60947-6-2 / maximum
1/h 300
 
Control circuit:
Design of activation   conventional
Design of the surge suppressor   with varistor
Type of voltage / of the controlled supply voltage   DC
Control supply voltage frequency    
  • 1 / rated value
Hz 50
  • 2 / rated value
Hz 60
Control supply voltage / 1    
  • for DC / rated value
V 24
Operating range factor control supply voltage rated value / of the magnet coil    
  • for DC
  0.85 1.1
Pull-in power / of the solenoid / for DC W 5.9
Holding power / of the solenoid / for DC W 5.9
Resistive loss / of the magnet coil / for DC    
  • typical
W 4
 
Auxiliary circuit:
Product extension / auxiliary switch   No
Contact reliability / of the auxiliary contacts   < 1 error per 100 million operating cycles
Number of NC contacts / for auxiliary contacts    
  • instantaneous switching
  3
  • lagging switching
  0
Number of NO contacts / for auxiliary contacts    
  • instantaneous switching
  3
  • leading switching
  0
Operating current / of the auxiliary contacts    
  • at AC-12 / maximum
A 10
  • at AC-15
   
  • at 230 V
A Назад в раздел