| | Similar to image | | SWITCH DISCONNECTOR WITH FUSE IN NEW DESIGN IU=160 A, UE=690 V, 3-POLE FOR NH FUSE SIZE 00 BASIC VERSION WITHOUT 8UC6 GRIP AND SHAFT WITHOUT LYRE CONTACTS |
| |
| General technical details: |
| product brand name | | SENTRON |
| product designation | | Switch Disconnector with Fuses 3KL |
| Number of poles | | 3 |
| Installation size of fuse-link | | 00 and 000 |
| Installation size of disconnecting link | | 00 and 000 |
| Acceptability for application | | |
| | | Yes |
| | | Yes |
| | | No |
| | | Yes |
- maintenance/repair switch
| | Yes |
| Product extension | | |
| | | No |
- optional / voltage trigger
| | No |
| Design of the operating mechanism | | manual operating mechanism |
| Product equipment / interlock | | Yes |
| Type from device | | fixed mounting |
| type of voltage | | AC/DC |
| Continuous current / rated value | A | 160 |
| Breaking capacity limit short-circuit current (lcu) / at 400 V / rated value | | |
| | | Yes |
| | | Yes |
| Active power loss | | |
| | W | 36 |
| | W | 12 |
| Insulation voltage / rated value | V | 1,000 |
| Impulse voltage resistance / rated value | V | 8,000 |
| Item designation | | |
- according to DIN EN 61346-2
| | Q |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | Q |
| Fuse system | | LV HRC fuse |
| |
| Main circuit: |
| Design of the electrical connection | | |
| | | flat connector |
| Number of poles / for main current circuit | | 3 |
| Operating current | | |
| | | |
| | A | 160 |
| | A | 160 |
| | A | 160 |
| | | |
| | A | 160 |
| | A | 160 |
| | A | 160 |
| | | |
| | A | 160 |
| | A | 160 |
| | A | 160 |
| | | |
| | A | 160 |
| | | |
| | A | 160 |
| Service power | | |
| | | |
- at 400 V / at 50/60 Hz / rated value
| W | 80,000 |
- at 500 V / at 50/60 Hz / rated value
| W | 80,000 |
- at 690 V / at 50/60 Hz / rated value
| W | 110,000 |
| Operating voltage / for DC / rated value | V | 440 |
| Operating voltage / at 50/60 Hz / for AC / rated value | V | 690 |
| |
| |
| Auxiliary circuit: |
| Number of NC contacts / for auxiliary contacts | | 0 |
| Number of NO contacts / for auxiliary contacts | | 0 |
| Number of change-over switches / for auxiliary contacts | | 0 |
| |
| Installation/mounting/dimensions: |
| Built in orientation | | any |
| Protection against electrical shock | | finger-safe |
| Design of the load switch | | |
| | | No |
| Type of the driving mechanism | | |
| | | No |
| Type of mounting | | surface mounting and installation |
| | | No |
- front mounting with central fixation
| | No |
- front mounting with 4-hole fixation
| | No |
| Width | mm | 185 |
| Height | mm | 125 |
| Depth | mm | 143 |
| |
| |
| Ambient conditions: |
| Ambient temperature | | |
| | °C | -25… +55 |
| | °C | -50… +80 |
| Protection class IP | | IP00 |
| Verification of suitability | | CE |
| |
| Certificates/approvals: |
| General Product Approval | other | | | | | ROSTEST | Manufacturer | | |
| |
| Further information: |
| Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/lowvoltage/catalogs |
| Industry Mall (Online ordering system) http://www.siemens.com/lowvoltage/mall |
| Service&Support (Manuals, Certificates, Characteristics, FAQs,...) http://support.automation.siemens.com/WW/view/en/3KL5330-1AA01/all |
| Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...) http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3KL5330-1AA01 |
| CAx-Online-Generator http://www.siemens.com/cax |
| Tender specifications Datanorm GAEB81 GAEB83 RTF TXT |
| |
| |
| |
| last change: | Feb 27, 2012 |