193-EC2CB - 193-EC2, E3 Plus Electronic Motor Protection Relay, 4 Inputs 2 Outputs, PTC thermistor input, DeviceLogix Series B, Internal ground fault sensor, Direct Contactor Mount, 5-25A - Quad Industry GmbH
|
Plan View Drawings (3D Format)
Catalog Number | Page | AutoCAD® DWG | DXF | Adobe® PDF | Windows Metafile |
---|---|---|---|---|---|
193-EC2CB | ABOLF030.DWG | ABOLF030.DXF | ABOLF030.PDF | ABOLF030.WMF |
3 View Dimension Drawings (3D Format) | |||||||||||||
|
Short Circuit Ratings |
Operational Rating | Dual Element Time Delay Fuses | Circuit Breakers | Rating Reference | File Ref: UL | File Ref: CSA | Comments | ||||||||
SCCR [kA] | Max Fuse Size [A] | Fuse Class | CB Type | UL CMC Type | Catalog Numbers | SCCR [kA] | SCCR [kA] | SCCR [kA] | SCCR [kA] | |||||
600V | 480V | 480Y/277V | 600V | 600Y/347V | ||||||||||
FLC: 5.0…25 Amps | 100 | 20 | CC,J | UL 508 Manual Motor Controller | -- | -- | -- | -- | -- | -- | Instruction Sheet | E14840 | cULus | For Use with 100-C09 or larger |
FLC: 5.0…25 Amps | 100 | 30 | CC,J | UL 508 Type E Comb. Motor Controller | E (3 Comp) | TBD | TBD | TBD | TBD | TBD | Instruction Sheet | E14840 | cULus | For Use with 100-C16 or larger |
FLC: 5.0…25 Amps | 100 | 40 | CC,J | UL 489 MCCB | C | 140U-D6D*-C30 | -- | 65 | -- | 25 | Instruction Sheet | E14840 | cULus | For Use with 100-C09 or larger |
FLC: 5.0…25 Amps | -- | -- | -- | UL 489 MCP | -- | -- | -- | -- | -- | -- | Instruction Sheet | E14840 | cULus | -- |
193EC2CB
193EC-2CB
193-EC2CB
193EC 2CB
193 EC2CB
Назад в раздел
![]() ![]() ![]() ![]() |
Quad Industry GmbH
GER + 49 (30) 994-049-88 E-mail: sales@quad-industry.com |