art.1SVR730841R0200 - CM-SRS.11S Current monitoring relay 1c/o, B-C=3mA-1A RMS, 110-130VAC (The CM-SRS.11S is a single-functional current monitoring relay from the CM single-phase monitors range. This monitoring relay operates with a rated control supply voltage of 110 - 130 V | Quad Industry GmbH

Артикул: 1SVR730841R0200
Наименование: CM-SRS.11S Current monitoring relay 1c/o, B-C=3mA-1A RMS, 110-130VAC (The CM-SRS.11S is a single-functional current monitoring relay from the CM single-phase monitors range. This monitoring relay operates with a rated control supply voltage of 110 - 130 V AC and has a 1 c/o (SPDT) output contact rated at 250 V / 4 A. It provides a RMS measuring principle for DC and AC currents with 3 measuring ranges: 3-30 mA, 10-100 mA and 0.1-1 A and works according to the open-circuit principle. The CM-SRS.11S is configurable for over- or undercurrent monitoring, the hysteresis is adjustable within a range of 3 to 30 % of the threshold value. A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.)
Производитель: ABB
Картинки описания: 2CDC251055V0011_720.jpg, 2CDC251244F0005_2CDC251245F0005_2CDC251247F0005_720.jpg, 2CDC251054V0011_720.jpg, 2CDC251058V0011_720.jpg, Gruppenbild_CM_einphasig_internet_720.jpg, single-phase_monitors_720.jpg


CM-SRS.11S

General Information

  • Extended Product Type:
    CM-SRS.11S
  • Product ID:
    1SVR730841R0200
  • EAN:
    4016779852289
  • Catalog Description:
    CM-SRS.11S Current monitoring relay 1c/o, B-C=3mA-1A RMS, 110-130VAC
  • Long Description:
    The CM-SRS.11S is a single-functional current monitoring relay from the CM single-phase monitors range. This monitoring relay operates with a rated control supply voltage of 110 - 130 V AC and has a 1 c/o (SPDT) output contact rated at 250 V / 4 A. It provides a RMS measuring principle for DC and AC currents with 3 measuring ranges: 3-30 mA, 10-100 mA and 0.1-1 A and works according to the open-circuit principle. The CM-SRS.11S is configurable for over- or undercurrent monitoring, the hysteresis is adjustable within a range of 3 to 30 % of the threshold value. A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.

Ordering

  • EAN:
    4016779852289
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85364900

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    97 mm
  • Package Level 1 Height:
    109 mm
  • Package Level 1 Length:
    30 mm
  • Package Level 1 Gross Weight:
    0.183 kg

Dimensions

  • Product Net Width:
    22.5 mm
  • Product Net Depth:
    103.7 mm
  • Product Net Height:
    85.6 mm
  • Product Net Weight:
    0.161 kg

Technical

  • Function:
    Over- or undercurrent monitoring
  • Measuring Range:
    3 ... 30 mA
    10 ... 100 mA
    0.1 ... 1 A
  • Rated Control Supply Voltage (Us):
    110 ... 130 V AC
  • Output:
    1 c/o (SPDT) contact
  • Terminal Type:
    Screw Terminals
  • Rated Operational Current AC-12 (Ie):
    (230 V) 4 A
  • Rated Operational Current AC-15 (Ie):
    (230 V) 3 A
  • Rated Operational Current DC-12 (Ie):
    (24 V) 4 A
  • Rated Operational Current DC-13 (Ie):
    (24 V) 2 A
  • Minimum Switching Capacity:
    24 V
    10 mA
  • Rated Insulation Voltage (Ui):
    Measuring Circuit / Output Circuit 600 V
    Output Circuit 1 / Output Circuit 2 250 V
    Supply Circuit / Measuring Circuit 600 V
    Supply Circuit / Output Circuit 250 V
  • Rated Impulse Withstand Voltage (Uimp):
    Measuring Circuit / Output Circuit 6 kV
    Output Circuit 1 / Output Circuit 2 4 kV
    Supply Circuit / Measuring Circuit 6 kV
    Supply Circuit / Output Circuit 4 kV
  • Degree of Protection:
    Housing IP50
    Terminals IP20
  • Overvoltage Category:
    III
  • Pollution Degree:
    3
  • Short-Circuit Protective Devices:
    Output Circuit NC - F Type Fuses 6 A
    Output Circuit NO - F Type Fuses 10 A
  • Electrical Durability:
    AC-12 100000 cycle
  • Mechanical Durability:
    30000000 cycle
  • Connecting Capacity:
    Flexible with Ferrule 1x 0.5 ... 2.5 mm??
    Flexible with Ferrule 2x 0.5 ... 1.5 mm??
    Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm??
    Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm??
    Flexible 1x 0.5 ... 2.5 mm??
    Flexible 2x 0.5 ... 1.5 mm??
    Rigid 1x 0.5 ... 4 mm??
    Rigid 2x 0.5 ... 2.5 mm??
  • Tightening Torque:
    0.6 ... 0.8 N??m
  • Wire Stripping Length:
    8 mm
  • Mounting Position:
    Any
  • Mounting on DIN Rail:
    TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
    TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
  • Standards:
    EN 50178
    IEC/EN 60255-27
    IEC/EN 61000-6-2
    IEC/EN 61000-6-3
    UL 508
    CAN/CSA C22.2 No.14

Environmental

  • Ambient Air Temperature:
    Operation -20 ... +60 ??C
    Storage -40 ... +85 ??C
  • RoHS Status:
    Following EU Directive 2011/65/EC

Technical UL/CSA

  • Maximum Operating Voltage UL/CSA:
    Output Circuit 300 V AC
  • Contact Rating UL/CSA:
    B300
  • Connecting Capacity UL/CSA:
    Flexible 1x 18-14 AWG
    Flexible 2x 18-16 AWG
    Rigid 1x 20-12 AWG
    Rigid 2x 20-14 AWG
  • Tightening Torque UL/CSA:
    7.08 in??lb

Certificates and Declarations (Document Number)

Classifications

  • Object Classification Code:
    B
  • E-nummer:
    3860631
  • ETIM 4:
    EC001440 - Current monitoring relay
  • ETIM 5:
    EC001440 - Current monitoring relay
  • ETIM 6:
    EC001440 - Current monitoring relay
  • eClass:
    7.0 27371802




Image 0 alt text

Categories

  • Products ?? Low Voltage Products and Systems ?? Control Products ?? Electronic Relays and Controls ?? Single Phase Monitors


Назад в раздел