art.1SBL417201R7000 - AF75-40-00 100-250V 50Hz / 100-250V 60Hz / 100-250V DC Contactor (AF75 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...) and generally for controlling power circuits up to 690 V AC an | Quad Industry GmbH
Àðòèêóë: 1SBL417201R7000
Íàèìåíîâàíèå: AF75-40-00 100-250V 50Hz / 100-250V 60Hz / 100-250V DC Contactor (AF75 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...) and generally for controlling power circuits up to 690 V AC and 440 V DC. The contactors can also be used for many other applications such lighting... The AF... contactors are fitted with an electronic coil interface which accepts a wide control voltage range, on AC 50/60 Hz or DC supplies. The same contactor can accept various supply voltages according to the different countries where the electrical equipment will be installed, or some fluctuation in the control voltage due to the local supply or network. The AF... contactors are also fully suitable for operation in AC or DC control circuit liable to voltage interruptions or voltage dip risks. Advantages: - Wide voltage range, e.g. 100 ... 250 V AC and DC - Can manage large voltage variations - Reduced power consumption - Very distinct closing and opening - Noise free - Can withstand voltage interruptions or voltage dips in the control supply (òÉä 20 ms). The AF... series 4-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 4 N.O. main poles, front and side-mounted add-on auxiliary contact blocks - Control circuit: AC or DC operated - Accessories: a wide range of accessories is available.)
Ïðîèçâîäèòåëü: ABB
AF75-40-00 100-250V 50Hz / 100-250V 60Hz / 100-250V DC
General Information
Extended Product Type:
AF75-40-00 100-250V 50Hz / 100-250V 60Hz / 100-250V DC
Product ID:
1SBL417201R7000
EAN:
3471522115300
Catalog Description:
AF75-40-00 100-250V 50Hz / 100-250V 60Hz / 100-250V DC Contactor
Long Description:
AF75 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...) and generally for controlling power circuits up to 690 V AC and 440 V DC. The contactors can also be used for many other applications such lighting... The AF... contactors are fitted with an electronic coil interface which accepts a wide control voltage range, on AC 50/60 Hz or DC supplies. The same contactor can accept various supply voltages according to the different countries where the electrical equipment will be installed, or some fluctuation in the control voltage due to the local supply or network. The AF... contactors are also fully suitable for operation in AC or DC control circuit liable to voltage interruptions or voltage dip risks. Advantages: - Wide voltage range, e.g. 100 ... 250 V AC and DC - Can manage large voltage variations - Reduced power consumption - Very distinct closing and opening - Noise free - Can withstand voltage interruptions or voltage dips in the control supply (òÉä 20 ms). The AF... series 4-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 4 N.O. main poles, front and side-mounted add-on auxiliary contact blocks - Control circuit: AC or DC operated - Accessories: a wide range of accessories is available.
acc. to IEC 60947-4-1, Open Contactors q = 40 ??C 125 A
Rated Operational Current AC-1 (Ie):
(690 V) 40 ??C 125 A (690 V) 55 ??C 105 A (690 V) 70 ??C 85 A
Rated Operational Current AC-3 (Ie):
(220 / 230 / 240 V) 55 ??C 75 A (380 / 400 V) 55 ??C 75 A (415 V) 55 ??C 72 A (440 V) 55 ??C 70 A (500 V) 55 ??C 65 A (690 V) 55 ??C 46 A
Short-Circuit Protective Devices:
gG Type Fuses 160 A
Rated Short-time Withstand Current (Icw):
at 40 ??C Ambient Temp, in Free Air, from a Cold State 10 s 650 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 15 min 135 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 1 min 250 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 30 s 370 A
Maximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A
Maximum Electrical Switching Frequency:
AC-1 300 cycles per hour AC-2 / AC-4 150 cycles per hour AC-3 300 cycles per hour
Rated Insulation Voltage (Ui):
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp):
8 kV
Maximum Mechanical Switching Frequency:
300 cycles per hour
Rated Control Circuit Voltage (Uc):
50 Hz 100 òÀæ 250 V 60 Hz 100 òÀæ 250 V DC Operation 100 òÀæ 250 V
Coil Consumption:
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 210 V??A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 210 V??A Holding at Max. Rated Control Circuit Voltage 60 Hz 7 V??A Holding at Max. Rated Control Circuit Voltage 60 Hz 2.8 W Holding at Max. Rated Control Circuit Voltage 50 Hz 7 V??A Holding at Max. Rated Control Circuit Voltage 50 Hz 2.8 W
Operate Time:
Between Coil Energization and NO Contact Closing 30 ... 100 ms Between Coil De-energization and NO Contact Opening 30 ... 110 ms Between Coil De-energization and NC Contact Closing 35 ... 115 ms
Connecting Capacity Main Circuit:
Flexible with Cable End 6 ... 16 mm?? Rigid Cable 6 ... 25 mm??
Connecting Capacity Auxiliary Circuit:
Flexible with Cable End 0.75 ... 2.5 mm?? Rigid Cable 1 ... 4 mm??
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Terminal Type:
Screw Terminals
Environmental
Ambient Air Temperature:
Near Contactor for Operation in Free Air -40 ... +70 ??C Close to Contactor for Storage -60 ... +80 ??C
Maximum Operating Altitude Permissible:
3000 m
Resistance to Shock acc. to IEC 60068-2-27:
Shock Direction: A 20 g Closed, Shock Direction: B1 10 g Open, Shock Direction: B1 5 g Shock Direction: B2 15 g Shock Direction: C1 20 g Shock Direction: C2 20 g