art.1SBL419210R8700 - AE75-40-00RT 125V DC Contactor (AE75 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...) and generally for controlling power circuits up to 690 V AC and 440 V DC. The contactors can als | Quad Industry GmbH
Àðòèêóë: 1SBL419210R8700
Íàèìåíîâàíèå: AE75-40-00RT 125V DC Contactor (AE75 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...) and generally for controlling power circuits up to 690 V AC and 440 V DC. The contactors can also be used for many other applications such lighting... The AE..RT contactors are the Ring Tongue terminal version of the AE... range. The AE... series 4-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 4 N.O. main poles, front and side-mounted add-on auxiliary contact blocks - Control circuit: DC operated with standard double-winding DC coils (with add-on factory-mounted lagging contact for insertion of the"holding" winding) - Accessories: a wide range of accessories is available.)
Ïðîèçâîäèòåëü: ABB
AE75-40-00RT 125V DC
General Information
Extended Product Type:
AE75-40-00RT 125V DC
Product ID:
1SBL419210R8700
EAN:
3471522244673
Catalog Description:
AE75-40-00RT 125V DC Contactor
Long Description:
AE75 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...) and generally for controlling power circuits up to 690 V AC and 440 V DC. The contactors can also be used for many other applications such lighting... The AE..RT contactors are the Ring Tongue terminal version of the AE... range. The AE... series 4-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 4 N.O. main poles, front and side-mounted add-on auxiliary contact blocks - Control circuit: DC operated with standard double-winding DC coils (with add-on factory-mounted lagging contact for insertion of the"holding" winding) - Accessories: a wide range of accessories is available.
Devices complying with international standards IEC 947-1 / 947-4-1 and European standards EN 60 947-1 / 60 947-4-1. Electromagnetic compatibility (EMC) according to amendment A11 to IEC 947-1; EN 60 947-1 and amendment 2 to IEC 947-4-1
Rated Operational Voltage:
Main Circuit 1000 V
Conventional Free-air Thermal Current (Ith):
acc. to IEC 60947-4-1, Open Contactors q = 40 °C 125 A
Rated Operational Current AC-1 (Ie):
(690 V) 70 °C 85 A
Rated Operational Current AC-3 (Ie):
(1000 V) 55 °C 28.0 A (220 / 230 / 240 V) 55 °C 75.0 A (380 / 400 V) 55 °C 75.0 A (415 V) 55 °C 72.0 A (440 V) 55 °C 70.0 A (500 V) 55 °C 65.0 A (690 V) 55 °C 46.0 A
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
10 x Ie AC-3
Short-Circuit Protective Devices:
gG Type Fuses 160 A
Rated Short-time Withstand Current (Icw):
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 650.0 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 125.0 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250.0 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000.0 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 370.0 A
Maximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A
Maximum Electrical Switching Frequency:
AC-1 300.0 cycles per hour AC-2 / AC-4 150.0 cycles per hour AC-3 300.0 cycles per hour
Rated Insulation Voltage (Ui):
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp):
8 kV
Mechanical Durability:
10 million
Maximum Mechanical Switching Frequency:
3600 cycles per hour
Coil Operating Limits:
(acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) °C
Rated Control Circuit Voltage (Uc):
DC Operation 125 V
Coil Consumption:
Average Holding Value, from Warm State 4 W Average Pull-in Value, from Cold State 200 W Pull-in at Max. Rated Control Circuit Voltage DC 200 W
Operate Time:
Between Coil Energization and NO Contact Closing 30 ... 30 ms Between Coil Energization and NC Contact Opening 10 ... 27 ms
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
Terminal Type:
Ring-Tongue Terminals
Environmental
Ambient Air Temperature:
Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °C Near Contactor for Operation in Free Air (Uc) -40 ... +70 °C Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand:
acc. to IEC 68-2-30 and 68-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible:
3000 m
Resistance to Shock acc. to IEC 60068-2-27:
Shock Direction: A 20 g Closed, Shock Direction: B1 10 g Open, Shock Direction: B1 5 g Shock Direction: B2 15 g Shock Direction: C1 20 g Shock Direction: C2 20 g
RoHS Status:
Following EU Directive 2002/95/EC August 18, 2005 and amendment