art.1SBL419025R8211 - GAE75-10-11 42V DC Contactor (GAE75 contactors are designed for DC circuit switching. Arc suppression is more difficult in DC than in AC. To choose a contactor, it is necessary to know the current and voltage to be broken as well as the L/R time constant | Quad Industry GmbH
Àðòèêóë: 1SBL419025R8211
Íàèìåíîâàíèå: GAE75-10-11 42V DC Contactor (GAE75 contactors are designed for DC circuit switching. Arc suppression is more difficult in DC than in AC. To choose a contactor, it is necessary to know the current and voltage to be broken as well as the L/R time constant of the power circuit to be controlled. GAE 75 contactors are of the block type design. - Main poles: the contactors are fitted with arc chutes with permanent magnets specially designed for DC breaking. The three contactor paths are arranged in series via two supplied and fitted insulated connections (25 mm??). The GAE75 are "single-pole" devices for which the connection polarities indicated next to the connection terminals must be respected. Furthermore, they are marked 1L1 for the positive terminal and 2T1 for the negative terminal. - Auxiliary contact: 1 CAL 5-11 side-mounted add-on auxiliary contact block (GAE75-10-11 types) - Control circuit: DC operated with standard double-winding DC coils (with add-on factory-mounted lagging contact for insertion of the"holding" winding) - Accessories: a wide range of accessories is available)
Ïðîèçâîäèòåëü: ABB
GAE75-10-11 42V DC
General Information
Extended Product Type:
GAE75-10-11 42V DC
Product ID:
1SBL419025R8211
EAN:
3471522113825
Catalog Description:
GAE75-10-11 42V DC Contactor
Long Description:
GAE75 contactors are designed for DC circuit switching. Arc suppression is more difficult in DC than in AC. To choose a contactor, it is necessary to know the current and voltage to be broken as well as the L/R time constant of the power circuit to be controlled. GAE 75 contactors are of the block type design. - Main poles: the contactors are fitted with arc chutes with permanent magnets specially designed for DC breaking. The three contactor paths are arranged in series via two supplied and fitted insulated connections (25 mm??). The GAE75 are "single-pole" devices for which the connection polarities indicated next to the connection terminals must be respected. Furthermore, they are marked 1L1 for the positive terminal and 2T1 for the negative terminal. - Auxiliary contact: 1 CAL 5-11 side-mounted add-on auxiliary contact block (GAE75-10-11 types) - Control circuit: DC operated with standard double-winding DC coils (with add-on factory-mounted lagging contact for insertion of the"holding" winding) - Accessories: a wide range of accessories is available
acc. to IEC 60947-4-1, Open Contactors q = 40 ??C 125 A acc. to IEC 60947-5-1, q = 40 ??C 16 A
Rated Operational Current AC-15 (Ie):
(220 / 240 V) 4 A (24 / 127 V) 6 A (380 / 440 V) 3 A (500 V) 2 A (690 V) 2 A
Short-Circuit Protective Devices:
Auxiliary Circuit - gG Type Fuses 10 A gG Type Fuses 160 A
Rated Short-time Withstand Current (Icw):
at 40 ??C Ambient Temp, in Free Air, from a Cold State 10 s 650 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 15 min 135 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 1 min 250 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 30 s 370 A for 0.1 s 140 A for 1 s 100 A
Maximum Electrical Switching Frequency:
300 cycles per hour
Rated Operational Current DC-1 (Ie):
(440 V) 55 ??C 100 A
Rated Operational Current DC-3 (Ie):
(440 V) 85 A
Rated Operational Current DC-5 (Ie):
(220 V) 85 A (440 V) 35 A
Rated Operational Current DC-13 (Ie):
(125 V) 0.55 / 69 A (24 V) 6 / 144 A (250 V) 0.3 / 75 A (48 V) 2.8 / 134 A (72 V) 1 / 72 A
Rated Insulation Voltage (Ui):
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp):
8 kV
Mechanical Durability:
5 million
Maximum Mechanical Switching Frequency:
3600 cycles per hour
Coil Operating Limits:
(acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at ?? òÉä 55 ??C) ??C
Rated Control Circuit Voltage (Uc):
DC Operation 42 V
Coil Consumption:
Average Holding Value, from Warm State 4 W Average Pull-in Value, from Cold State 200 W Holding at Max. Rated Control Circuit Voltage DC 4 W Pull-in at Max. Rated Control Circuit Voltage DC 200 W
Operate Time:
Between Coil Energization and NO Contact Closing 30 ... 30 ms Between Coil De-energization and NO Contact Opening 5 ... 15 ms Between Coil De-energization and NC Contact Closing 8 ... 18 ms Between Coil Energization and NC Contact Opening 10 ... 27 ms
Connecting Capacity Main Circuit:
Flexible with Cable End 6 ... 16 mm?? Rigid Cable 6 ... 25 mm??
Connecting Capacity Auxiliary Circuit:
Flexible with Cable End 0.75 ... 2.5 mm?? Rigid Cable 1 ... 4 mm??
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
Connecting terminals (delivered in open position) Main poles:
M 6 (+,-) pozidriv 2 screws with 1x (13 x 10 mm) connector
Terminal Type:
Screw Terminals
Environmental
Ambient Air Temperature:
Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 ??C Near Contactor for Operation in Free Air (Uc) -40 ... +70 ??C Close to Contactor for Storage -60 ... +80 ??C
Climatic Withstand:
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II