art.1SBL241001R8410 - A26-30-10 110V 50Hz / 110-120V 60Hz Contactor | Quad Industry GmbH

Àðòèêóë: 1SBL241001R8410
Íàèìåíîâàíèå: A26-30-10 110V 50Hz / 110-120V 60Hz Contactor<br>A26 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capacitor switching, lighting. The A... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles, 1 built-in auxiliary contact, front and side-mounted add-on auxiliary contact blocks - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.
Ïðîèçâîäèòåëü: ABB


A26-30-10 110V 50Hz / 110-120V 60Hz

General Information

  • Extended Product Type:
    A26-30-10 110V 50Hz / 110-120V 60Hz
  • Product ID:
    1SBL241001R8410
  • EAN:
    3471522062840
  • Catalog Description:
    A26-30-10 110V 50Hz / 110-120V 60Hz Contactor
  • Long Description:
    A26 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capacitor switching, lighting. The A... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles, 1 built-in auxiliary contact, front and side-mounted add-on auxiliary contact blocks - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.

Ordering

  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85364900

Popular Downloads

Dimensions

  • Product Net Width:
    54 mm
  • Product Net Depth:
    93.6 mm
  • Product Net Height:
    90 mm
  • Product Net Weight:
    0.600 kg

Technical

  • Number of Main Contacts NO:
    3
  • Number of Main Contacts NC:
    0
  • Number of Auxiliary Contacts NO:
    1
  • Number of Auxiliary Contacts NC:
    0
  • Rated Operational Voltage:
    Main Circuit 690 V
  • Rated Frequency (f):
    Supply Circuit 50 Hz
    Supply Circuit 60 Hz
  • Conventional Free-air Thermal Current (Ith):
    acc. to IEC 60947-4-1, Open Contactors q = 40 °C 45 A
    acc. to IEC 60947-5-1, q = 40 °C 16 A
  • Rated Operational Current AC-1 (Ie):
    (690 V) 40 °C 45 A
    (690 V) 55 °C 40 A
    (690 V) 70 °C 32 A
  • Rated Operational Current AC-3 (Ie):
    (220 / 230 / 240 V) 55 °C 26 A
    (380 / 400 V) 55 °C 26 A
    (415 V) 55 °C 26 A
    (440 V) 55 °C 26 A
    (500 V) 55 °C 22 A
    (690 V) 55 °C 17 A
  • Rated Operational Power AC-3 (Pe):
    (220 / 230 / 240 V) 6.5 kW
    (380 / 400 V) 11 kW
    (415 V) 11 kW
    (440 V) 15 kW
    (500 V) 15 kW
    (690 V) 15 kW
  • Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
    8 x Ie AC-3
  • Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
    10 x Ie AC-3
  • Rated Operational Current AC-15 (Ie):
    (220 / 240 V) 4 A
    (24 / 127 V) 6 A
    (380 / 440 V) 3 A
    (500 V) 2 A
    (690 V) 2 A
  • Short-Circuit Protective Devices:
    Auxiliary Circuit - gG Type Fuses 10 A
    gG Type Fuses 50 A
  • Rated Short-time Withstand Current (Icw):
    at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 210 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 45 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 90 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 400 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 110 A
    for 0.1 s 140 A
    for 1 s 100 A
  • Maximum Breaking Capacity:
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 420 A
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 170 A
  • Maximum Electrical Switching Frequency:
    AC-1 600 cycles per hour
    AC-2 / AC-4 300 cycles per hour
    AC-3 1200 cycles per hour
  • Rated Operational Current DC-13 (Ie):
    (125 V) 1.1 / 138 A
    (24 V) 6 / 144 A
    (250 V) 0.55 / 138 A
    (48 V) 2.8 / 134 A
    (72 V) 2 / 144 A
  • Rated Insulation Voltage (Ui):
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
    acc. to UL/CSA 600 V
  • Rated Impulse Withstand Voltage (Uimp):
    8 kV
  • Mechanical Durability:
    10 million
  • Maximum Mechanical Switching Frequency:
    3600 cycles per hour
  • Coil Operating Limits:
    (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at ? ? 55 °C) °C
  • Rated Control Circuit Voltage (Uc):
    50 Hz 110 V
    60 Hz 110 … 120 V
  • Coil Consumption:
    Average Holding Value 50 / 60 Hz 12 V·A
    Average Holding Value 50 / 60 Hz 3 W
    Average Pull-in Value 50 Hz 125 V·A
    Average Pull-in Value 60 Hz 120 V·A
  • Operate Time:
    Between Coil Energization and NO Contact Closing 8 ... 21 ms
    Between Coil De-energization and NO Contact Opening 4 ... 11 ms
  • Connecting Capacity Main Circuit:
    Flexible with Cable End 0.75 ... 4 mm?
    Rigid Cable 1.5 ... 6 mm?
  • Connecting Capacity Auxiliary Circuit:
    Flexible with Cable End 0.75 ... 2.5 mm?
    Rigid Cable 1 ... 4 mm?
  • Degree of Protection:
    acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
  • Connecting terminals (delivered in open position) Main poles:
    M 4 (+,-) pozidriv 2 screws with cable clamp
  • Terminal Type:
    Screw Terminals

Environmental

  • Ambient Air Temperature:
    Close to Contactor Fitted with Thermal O/L Relay -25 ... +55 °C
    Close to Contactor for Storage -60 ... +80 °C
    Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +55 °C
    Close to Contactor without Thermal O/L Relay (Uc) -40 ... +70 °C
  • Climatic Withstand:
    acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
  • Maximum Operating Altitude Permissible:
    3000 m
  • Resistance to Shock acc. to IEC 60068-2-27:
    Shock Direction: A 20 g
    Closed, Shock Direction: B1 10 g
    Open, Shock Direction: B1 5 g
    Shock Direction: B2 15 g
    Shock Direction: C1 20 g
    Shock Direction: C2 20 g
  • RoHS Status:
    Following EU Directive 2002/95/EC August 18, 2005 and amendment

Certificates and Declarations (Document Number)

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    101 mm
  • Package Level 1 Length:
    115 mm
  • Package Level 1 Height:
    61 mm
  • Package Level 1 Gross Weight:
    0.6 kg
  • Package Level 1 EAN:
    3471522062840
  • Package Level 2 Units:
    24 piece
  • Package Level 3 Units:
    576 piece

Classifications

  • Object Classification Code:
    Q
  • E-nummer:
    3227743
  • ETIM 4:
    EC000066 - Magnet contactor, AC-switching
  • ETIM 5:
    EC000066 - Magnet contactor, AC-switching
  • ETIM 6:
    EC000066 - Power contactor, AC switching
  • UNSPSC:
    39121529

Where Used (as a spare part for "Products")

Identifier Unit Of Measure Qty Description
FC-0460-0020 piece 1 No Description Available



Categories

  • Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
  • Parts & Services » Drives » Low voltage AC drives » Legacy AC drives » MoCon


Íàçàä â ðàçäåë