art.1SBH143010R8631 - NL31ERT 110V DC | 1SBH143010R8631 | NL31ERT 110V DC | Quad Industry GmbH

Àðòèêóë: 1SBH143010R8631
Íàèìåíîâàíèå: NL31ERT 110V DC | 1SBH143010R8631 | NL31ERT 110V DC
Ïðîèçâîäèòåëü: ABB


General Information
Extended Product Type:
NL31ERT 110V DC
Product ID:
1SBH143010R8631
EAN:
3471522361967
Catalog Description:
NL31ERT 110V DC
 
Additional Information
ABB Industrial IT Suite:
Control IT
Ambient Air Temperature:
Near Contactor for Operation in Free Air (Uc) +55 ... +70 °C
Near Contactor for Operation in Free Air (0.85 - 1.1 Uc) -40 ... +55 °C
Close to Contactor for Storage -60 ... +80 °C
Catalog Description:
NL31ERT 110V DC
Climatic Withstand:
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Coil Consumption:
Average Holding Value, from Warm State 3 W
Average Pull-in Value, from Cold State 3 W
Coil Operating Limits:
(acc. to IEC 60947-5-1) 0.85 ... 1.1 x Uc (at ? ? 55 °C) °C
Coil Time Constant Closed L/R:
74 ms
Coil Time Constant Open L/R:
28 ms
Connecting Capacity-Auxiliary Circuit:
Rigid or Flexible with Cable Lug 0.75 ... 2.5 mm?
Connecting terminals (delivered in open position) Built-in auxiliary terminals:
M 3.5 (+,-) pozidriv 2 screw with conic washer
Connecting terminals (delivered in open position) Coils terminals:
M 3.5 (+,-) pozidriv 2 screw with conic washer
Conventional Free-air Thermal Current (Ith):
acc. to IEC 60947-5-1, q=40°C 16 A
Data Sheet, Technical Information:
1SBC101032D0201
Declaration of Conformity - CE:
1SBD250847C1000
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP10
Dimension Diagram:
FPTE307902
Drop-out Voltage in % of Uc:
10 … 30 %
EAN:
3471522361967
Environmental Information:
1SBD250127E1002
IIT Publishing Status:
Level 0 - Information enabled
Industrial IT Certification Level:
0
Instructions and Manuals:
1SBC101006M5501
Insulation Resistance:
(500V DC) After Durability Test 5 M?
Invoice Description:
NL31ERT 110V DC
Maximum Electrical Switching Frequency:
1200 cycles per hour
Maximum Mechanical Switching Frequency:
6000 cycles per hour
Maximum Operating Altitude Permissible:
3000 m
Maximum Permissible Short Supply Interruption Without Opening of Contacts:
2.5 ms
Mechanical Durability:
> 20 million
Minimum Switching Capacity with Failure Rate Below 10E-6:
17 V / 5 mA according to IEC 60947-5-4
Mounted Auxiliary Contacts 1st Stack:
3 NO, 1 NC
Mounted Auxiliary Contacts 2nd Stack:
0 NO, 0 NC
Mounting Position:
Position 1 to 5 -Ambient temperature =<55°C and control voltage 0.85 - 1.1 Uc, Ambient temperature 55 - 70°C and control voltage equal to Uc
Non-overlapping Time Between N.O. and N.C. Contacts:
>= 2 ms
Number of Auxiliary Contacts NC:
1
Number of Auxiliary Contacts NO:
3
Number of Main Contacts NC:
0
Number of Main Contacts NO:
0
Operate Time:
Between Coil Energization and N.O. Contact Closing 50 ... 100 ms
Between Coil De-energization and N.O. Contact Opening 10 ... 17 ms
Between Coil De-energization and N.C. Contact Closing 16 ... 27 ms
Between Coil Energization and N.C. Contact Opening 20 ... 70 ms
Package Level 1 Height:
78 mm
Package Level 1 Width:
44 mm
Power Loss:
Per Pole 0.1 W
Product Main Type:
NL31ERT
Product Name:
Block Contactor
Product Net Weight:
0.52 kg
Rated Breaking Capacity acc. to IEC 60947-5-1:
10 x Ie AC-15
Rated Control Circuit Voltage (Uc):
DC Operation 110 V
Rated Frequency (fr):
Supply Circuit 50 Hz
Supply Circuit 60 Hz
Rated Frequency Limits:
25 … 400 Hz
Rated Impulse Withstand Voltage (Uimp):
6 kV
Rated Insulation Voltage (Ui):
acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V
acc. to UL/CSA 600 V
Rated Making Capacity acc. to IEC 60947-5-1:
10 x Ie AC-15
Rated Operational Current AC-15 (Ie):
(220 / 240V) 4 A
(24 / 127V) 6 A
(380 / 440V) 3 A
(500V) 2 A
(690V) 2 A
Rated Operational Current DC-13 (Ie):
(125V) 0.55 / 69 A
(24V) 6 / 144 A
(250V) 0.3 / 75 A
(48V) 2.8 / 134 A
(72V) 1 / 72 A
Rated Operational Voltage (Ue):
Main Circuit 690 V
Auxiliary Circuit 690 V
Rated Short-time Withstand Current (Icw):
for 0.1s 140 A
for 1.0s 100 A
Resistance to Shock acc. to IEC 60068-2-27:
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: A 20 m/s?
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: A 10 m/s?
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C1 20 m/s?
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C1 8 m/s?
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C2 14 m/s?
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C2 8 m/s?
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: B1 15 m/s?
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B1 5 m/s?
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: B2 10 m/s?
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B2 10 m/s?
RoHS Date:
01 07 2006
RoHS Information:
1SBD350068R1000
RoHS Status:
Following EU Directive 2002/95/EC August 18, 2005 and amendment
Short-Circuit Protective Devices:
Auxiliary Circuit - gG Type Fuses 10 A


Íàçàä â ðàçäåë