art.1SBH901074R8140 - NX40E-81 24V 50/60Hz Contactor relay (NX...contactor relays are used for switching auxiliary circuits and control circuits. These contactor relays are of the block type design with: òÀÓ 4 poles. Contactor relays have mechanically linked auxiliary contact | Quad Industry GmbH
Àðòèêóë: 1SBH901074R8140
Íàèìåíîâàíèå: NX40E-81 24V 50/60Hz Contactor relay (NX...contactor relays are used for switching auxiliary circuits and control circuits. These contactor relays are of the block type design with: òÀÓ 4 poles. Contactor relays have mechanically linked auxiliary contact elements òÀÓ control circuit: AC operated òÀÓ add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.)
Ïðîèçâîäèòåëü: ABB
NX40E-81
General Information
Extended Product Type:
NX40E-81
Product ID:
1SBH901074R8140
EAN:
3471522390813
Catalog Description:
NX40E-81 24V 50/60Hz Contactor relay
Long Description:
NX...contactor relays are used for switching auxiliary circuits and control circuits. These contactor relays are of the block type design with: òÀÓ 4 poles. Contactor relays have mechanically linked auxiliary contact elements òÀÓ control circuit: AC operated òÀÓ add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
(220 / 240 V) 4 A (24 / 127 V) 6 A (400 / 440 V) 2 A (500 V) 2 A (690 V) 2 A (380 / 440 V) 3 A
Rated Short-time Withstand Current (Icw):
for 0.1 s 140 A for 1 s 100 A
Maximum Electrical Switching Frequency:
AC-15 1200 cycles per hour DC-13 900 cycles per hour
Rated Operational Current DC-13 (Ie):
(110 V) 0.55 A / 60 W (125 V) 0.55 A / 69 W (220 V) 0.30 A / 66 W (24 V) 6 A / 144 W (250 V) 0.30 A / 75 W (400 V) 2.8 A / 134 W (500 V) 1 A / 72 W
Rated Insulation Voltage (Ui):
acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage (Uimp):
6 kV
Maximum Mechanical Switching Frequency:
6000 cycles per hour
Rated Control Circuit Voltage (Uc):
50 Hz 24 V 60 Hz 24 V
Operate Time:
Between Coil De-energization and NC Contact Closing 9 ... 16 ms Between Coil De-energization and NO Contact Opening 4 ... 11 ms Between Coil Energization and NC Contact Opening 7 ... 21 ms Between Coil Energization and NO Contact Closing 10 ... 26 ms
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Terminal Type:
Screw Terminals
Environmental
Ambient Air Temperature:
Close to Contactor for Storage -60 ... +80 ??C Close to Contactor Fitted with Thermal O/L Relay -25 ... +55 ??C Close to Contactor without Thermal O/L Relay -40 ... +70 ??C Near Contactor for Operation in Free Air -40 ... +70 ??C
Climatic Withstand:
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible:
3000 m
RoHS Status:
Following EU Directive 2002/95/EC August 18, 2005 and amendment
Technical UL/CSA
Tightening Torque UL/CSA:
Auxiliary Circuit 9 in??lb Control Circuit 9 in??lb