AF30 contactors are used for controlling power circuits up to 690 V AC and 220 V DC. They are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads. AF... contactors include an electronic coil interface accepting a wide control voltage Uc min. ... Uc max. Only four coils cover control voltages between 24...500 V 50/60 Hz or 20...500 V DC. AF contactors can manage large control voltage variations. One coil can be used for different control voltages used worldwide without any coil change. AF contactors have built-in surge protection and do not require additional surge suppressors. The AF... series 2-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles with a non-removable front-mounted 1 N.O. + 1 N.C. auxiliary contact block, side-mounted add-on auxiliary contact blocks (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1 including the "Mechanically Linked" symbol on the contactor side. N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC or DC operated - Accessories: a wide range of accessories is available.
Note: 2-stack contactors available in some countries: please consult your ABB representative. AF..-30-..-11 not suitable for a direct control by PLC-output.
Ordering
EAN:
3471523111318
Minimum Order Quantity:
1 piece
Country of Origin:
France (FR)
Customs Tariff Number:
85369085
Dimensions
Product Net Width:
45 mm
Product Net Depth:
111.5 mm
Product Net Height:
86 mm
Product Net Weight:
0.350 kg
Container Information
Package Level 1 Units:
1 piece
Package Level 1 Width:
87 mm
Package Level 1 Length:
114 mm
Package Level 1 Height:
47 mm
Package Level 1 Gross Weight:
0.370 kg
Environmental
Ambient Air Temperature:
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 ??C
Close to Contactor for Storage -60 ... +80 ??C
Close to Contactor without Thermal O/L Relay -40 ... +70 ??C
Maximum Operating Altitude Permissible:
3000 m
Resistance to Shock acc. to IEC 60068-2-27:
Shock Direction: A 30 gn
Closed, Shock Direction: B1 25 gn
Open, Shock Direction: B1 5 gn
Shock Direction: B2 15 gn
Shock Direction: C1 25 gn
Shock Direction: C2 25 gn
Resistance to Vibrations acc. to IEC 60068-2-6:
5 ... 300 Hz 4 g Closed position / 2 g Open position
RoHS Status:
Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2008 Q1