art.1SBH143010R8131 - NL31ERT 24V DC Contactor Relay (NL... contactor relays are used for switching auxiliary circuits and control circuits - Poles: 4-pole contactor relays (mechanically linked contact elements available) - Control circuit: DC operated with solid core magnet c | Quad Industry GmbH
Àðòèêóë: 1SBH143010R8131
Íàèìåíîâàíèå: NL31ERT 24V DC Contactor Relay (NL... contactor relays are used for switching auxiliary circuits and control circuits - Poles: 4-pole contactor relays (mechanically linked contact elements available) - Control circuit: DC operated with solid core magnet circuit. The polarity on the coil terminals (A1+ and A2-) must be respected - Accessories: a wide range of accessories is available NL... contactors are fitted with low consumption DC coils and are suitable for a direct control by PLC outputs.)
Ïðîèçâîäèòåëü: ABB
NL31ERT 24V DC
General Information
Extended Product Type:
NL31ERT 24V DC
Product ID:
1SBH143010R8131
EAN:
3471522361912
Catalog Description:
NL31ERT 24V DC Contactor Relay
Long Description:
NL... contactor relays are used for switching auxiliary circuits and control circuits - Poles: 4-pole contactor relays (mechanically linked contact elements available) - Control circuit: DC operated with solid core magnet circuit. The polarity on the coil terminals (A1+ and A2-) must be respected - Accessories: a wide range of accessories is available NL... contactors are fitted with low consumption DC coils and are suitable for a direct control by PLC outputs.
(220 / 240 V) 4 A (24 / 127 V) 6 A (380 / 440 V) 3 A (500 V) 2 A (690 V) 2 A
Short-Circuit Protective Devices:
Auxiliary Circuit - gG Type Fuses 10 A
Rated Short-time Withstand Current (Icw):
for 0.1 s 140 A for 1 s 100 A
Maximum Electrical Switching Frequency:
1200 cycles per hour
Rated Operational Current DC-13 (Ie):
(125 V) 0.55 / 69 A (24 V) 6 / 144 A (250 V) 0.3 / 75 A (48 V) 2.8 / 134 A (72 V) 1 / 72 A
Rated Insulation Voltage (Ui):
acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp):
6 kV
Maximum Mechanical Switching Frequency:
6000 cycles per hour
Coil Operating Limits:
(acc. to IEC 60947-5-1) 0.85 ... 1.1 x Uc (at ?? òÉä 55 ??C) ??C
Rated Control Circuit Voltage (Uc):
DC Operation 24 V
Coil Consumption:
Average Holding Value, from Warm State 3 W Average Pull-in Value, from Cold State 3 W
Operate Time:
Between Coil Energization and NO Contact Closing 50 ... 100 ms Between Coil De-energization and NO Contact Opening 10 ... 17 ms Between Coil De-energization and NC Contact Closing 16 ... 27 ms Between Coil Energization and NC Contact Opening 20 ... 70 ms
Connecting Capacity Auxiliary Circuit:
Rigid or Flexible with Cable Lug 0.75 ... 2.5 mm??
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP10
Terminal Type:
Ring-Tongue Terminals
Environmental
Ambient Air Temperature:
Near Contactor for Operation in Free Air (Uc) +55 ... +70 ??C Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 ??C Close to Contactor for Storage -60 ... +80 ??C
Climatic Withstand:
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible:
3000 m
Resistance to Shock acc. to IEC 60068-2-27:
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: A 20 m/s?? Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: A 10 m/s?? Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C1 20 m/s?? Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C1 8 m/s?? Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C2 14 m/s?? Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C2 8 m/s?? Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: B1 15 m/s?? Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B1 5 m/s?? Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: B2 10 m/s?? Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B2 10 m/s??