art.1SBL163060R5110 - TAL12-30-10RT 17-32V DC Contactor (TAL12 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capa | Quad Industry GmbH
Àðòèêóë: 1SBL163060R5110
Íàèìåíîâàíèå: TAL12-30-10RT 17-32V DC Contactor (TAL12 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capacitor switching, lighting. The TAL..RT contactors are the Ring Tongue terminal version of the TAL... range. The TAL... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles, 1 built-in auxiliary contact, front and side-mounted add-on auxiliary contact blocks - Control circuit: DC operated with solid core magnet circuit. The polarity on the coil terminals (A1+ and A2-) must be respected - Accessories: a wide range of accessories is available. TAL... contactors are fitted with low consumption DC coils and offer a large coil voltage range.)
Ïðîèçâîäèòåëü: ABB
TAL12-30-10RT 17-32V DC
General Information
Extended Product Type:
TAL12-30-10RT 17-32V DC
Product ID:
1SBL163060R5110
EAN:
3471522362513
Catalog Description:
TAL12-30-10RT 17-32V DC Contactor
Long Description:
TAL12 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capacitor switching, lighting. The TAL..RT contactors are the Ring Tongue terminal version of the TAL... range. The TAL... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles, 1 built-in auxiliary contact, front and side-mounted add-on auxiliary contact blocks - Control circuit: DC operated with solid core magnet circuit. The polarity on the coil terminals (A1+ and A2-) must be respected - Accessories: a wide range of accessories is available. TAL... contactors are fitted with low consumption DC coils and offer a large coil voltage range.
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
10 x Ie AC-3
Rated Operational Current AC-15 (Ie):
(220 / 240 V) 4 A (24 / 127 V) 6 A (380 / 440 V) 3 A (500 V) 2 A (690 V) 2 A
Short-Circuit Protective Devices:
Auxiliary Circuit - gG Type Fuses 10 A gG Type Fuses 32 A
Rated Short-time Withstand Current (Icw):
at 40 ??C Ambient Temp, in Free Air, from a Cold State 10 s 120 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 15 min 28 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 1 min 55 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 1 s 280 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 30 s 70 A for 0.1 s 140 A for 1 s 100 A
Maximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 100 A
Maximum Electrical Switching Frequency:
AC-1 600 cycles per hour AC-2 / AC-4 300 cycles per hour AC-3 1200 cycles per hour
Rated Operational Current DC-13 (Ie):
(125 V) 1.1 / 138 A (24 V) 6 / 144 A (250 V) 0.55 / 138 A (48 V) 2.8 / 134 A (72 V) 2 / 144 A
Rated Insulation Voltage (Ui):
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp):
6 kV
Mechanical Durability:
10 million
Maximum Mechanical Switching Frequency:
3600 cycles per hour
Rated Control Circuit Voltage (Uc):
DC Operation 17 òÀæ 32 V
Coil Consumption:
Holding DC (Umin / Umax) 2.5 / 8.5 W Pull-in DC (Umin / Umax) 2.5 / 8.5 W
Operate Time:
Between Coil Energization and NO Contact Closing 50 ... 100 ms Between Coil De-energization and NO Contact Opening 10 ... 17 ms
Rigid or Flexible with Cable Lug 0.75 ... 2.5 mm??
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP10
Connecting terminals (delivered in open position) Main poles:
M 3.5 (+,-) pozidriv 2 screw with conic washer
Terminal Type:
Ring-Tongue Terminals
Environmental
Ambient Air Temperature:
Close to Contactor for Storage -60 ... +80 ??C Close to Contactor without Thermal O/L Relay -40 ... +55 ??C
Climatic Withstand:
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible:
3000 m
Resistance to Shock acc. to IEC 60068-2-27:
Closed, Shock Direction: A 20 g Open, Shock Direction: A 10 g Closed, Shock Direction: B1 15 g Open, Shock Direction: B1 5 g Shock Direction: B2 10 g Closed, Shock Direction: C1 20 g Open, Shock Direction: C1 8 g Closed, Shock Direction: C2 14 g Open, Shock Direction: C2 8 g
RoHS Status:
Following EU Directive 2002/95/EC August 18, 2005 and amendment