art.1SBL149061R6600 - TAE9-30-00 90-150V DC Contactor (TAE9 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capacit | Quad Industry GmbH
Àðòèêóë: 1SBL149061R6600
Íàèìåíîâàíèå: TAE9-30-00 90-150V DC Contactor (TAE9 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capacitor switching, lighting. The TAE... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles, front and side-mounted add-on auxiliary contact blocks - Control circuit: DC operated with standard double-winding DC coils (with add-on factory-mounted lagging contact for insertion of the"holding" winding). TAE... contactors offer a large coil voltage range - Accessories: a wide range of accessories is available.)
Ïðîèçâîäèòåëü: ABB
TAE9-30-00 90-150V DC
General Information
Extended Product Type:
TAE9-30-00 90-150V DC
Product ID:
1SBL149061R6600
EAN:
3471522236074
Catalog Description:
TAE9-30-00 90-150V DC Contactor
Long Description:
TAE9 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capacitor switching, lighting. The TAE... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles, front and side-mounted add-on auxiliary contact blocks - Control circuit: DC operated with standard double-winding DC coils (with add-on factory-mounted lagging contact for insertion of the"holding" winding). TAE... contactors offer a large coil voltage range - Accessories: a wide range of accessories is available.
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
10 x Ie AC-3
Short-Circuit Protective Devices:
gG Type Fuses 25 A
Rated Short-time Withstand Current (Icw):
at 40 ??C Ambient Temp, in Free Air, from a Cold State 10 s 100 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 15 min 26 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 1 min 50 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 1 s 250 A at 40 ??C Ambient Temp, in Free Air, from a Cold State 30 s 60 A
Maximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 100 A
Maximum Electrical Switching Frequency:
AC-1 600 cycles per hour AC-2 / AC-4 300 cycles per hour AC-3 600 cycles per hour
Rated Insulation Voltage (Ui):
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Impulse Withstand Voltage (Uimp):
8 kV
Mechanical Durability:
5 million
Maximum Mechanical Switching Frequency:
3600 cycles per hour
Rated Control Circuit Voltage (Uc):
DC Operation 90 òÀæ 150 V
Coil Consumption:
Holding DC (Umin / Umax) 1 / 3.5 W Pull-in DC (Umin / Umax) 65 / 140 W
Operate Time:
Between Coil Energization and NO Contact Closing 10 ... 16 ms Between Coil De-energization and NO Contact Opening 5 ... 14 ms
Connecting Capacity Main Circuit:
Flexible with Cable End 0.75 ... 2.5 mm?? Rigid Cable 1 ... 4 mm??
Connecting Capacity Auxiliary Circuit:
Flexible with Cable End 0.75 ... 2.5 mm?? Rigid Cable 1 ... 4 mm??
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
Connecting terminals (delivered in open position) Main poles:
M 3.5 (+,-) pozidriv 2 screws with cable clamp
Terminal Type:
Screw Terminals
Environmental
Ambient Air Temperature:
Close to Contactor Fitted with Thermal O/L Relay -25 ... +55 ??C Close to Contactor for Storage -60 ... +80 ??C Close to Contactor without Thermal O/L Relay -40 ... +55 ??C
Climatic Withstand:
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible:
3000 m
RoHS Status:
Following EU Directive 2002/95/EC August 18, 2005 and amendment