- Temperature range
0 ... 200 В°C (0 ... 392 В°F)
Datasheet as PDF in following languages: Technical Data: NJ4-30GM-N-200-Y128005General specifications | Switching element function | NAMUR, NC | Rated operating distance | 4 mm | Installation | flush | Output polarity | NAMUR | Assured operating distance | 0 ... 3.04 mm | Reduction factor rAl | 0.4 | Reduction factor rCu | 0.3 | Reduction factor r304 | 0.85 | Nominal ratings | Nominal voltage | 8 V | Switching frequency | 0 ... 1000 Hz | Hysteresis | typ. % | Current consumption | | | Measuring plate not detected | min. 3 mA | | Measuring plate detected | ≤ 1 mA | Compliance with standards and directives | Standard conformity | | | NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | Approvals and certificates | UL approval | cULus Listed, General Purpose | CSA approval | cCSAus Listed, General Purpose | Ambient conditions | Ambient temperature | 0 ... 200 В°C (32 ... 392 В°F) | Mechanical specifications | Connection type | cable SIHF , 5 m | Core cross-section | 0.34 mm2 | Housing material | Stainless steel 1.4305 / AISI 303 | Sensing face | PPS | Housing diameter | 30 mm | Protection degree | IP65 | Note | amplifier -25В°C...70В°C 1 m PTFE cable between amplifier and oscillator | General information | Use in the hazardous area | see instruction manuals | | Category | 1G; 2G |
|