2531UP - KNX Devices
Flush-mounted room climate interface
with satellite input
3 binary inputs
1 blinds output, 1 output "TRIAC" (heating) - Quad Industry GmbH
Артикул: 2531UP
Наименование: KNX Devices
Flush-mounted room climate interface
with satellite input
3 binary inputs
1 blinds output, 1 output "TRIAC" (heating)
Производитель: JUNG
|
|
KNX Devices
Flush-mounted room climate interface
with satellite input
3 binary inputs
1 blinds output, 1 output "TRIAC" (heating)
Intended use
* Switching of electrically-driven blinds, awnings and similar blinds for AC 230 V mains voltage
* Switching of electrothermal actuators
* Installation in appliance box to DIN 49073
* Connection with enclosed terminals
Product characteristics
* Control of Venetian blinds, awnings and similar blinds
* Control of electrothermal actuators
* Three binary inputs for potential-free contacts, usable as extension inputs for local operation
* Supply via bus, no additional power supply necessary
Blinds function
* Blind position directly controllable
* Slat position directly controllable
* Feedback of movement status, blind position and slat position
* Forced position through higher-level controller
* Safety function: 3 independent wind alarms, rain alarm, frost alarm
* Sun protection function
Function of valve drives
* Switching operation or PWM operation
* Valve drives with characteristics opened or closed without power
* Overload-protected, short circuit-protected
* Protection against jamming valves
* Forced position
* Cyclical monitoring of the input signals configurable
PWM operation: electrothermal actuators only have the positions Open and Closed. In PWM operation, switch-on and switch-off during the drive’s cycle time achieves an almost constant behaviour.
Technical data
Rated voltage: AC 230/240 V ~, 50/60 Hz
Switching voltage: AC 250 V ~
Ambient temperature: ?5 ... +45 °C
Storage/transport temperature: ?25 ... +70 °C
Blinds output
Contact type: µ
Switching current AC1 (cos ? > 0.8): 3 A
Min. switching current AC: 100 mA
Motors (230 V): 600 VA
Heating output
Contact type: semiconductor (triac), ?
Switching current: 5 ... 25 mA
Switch-on current: max. 600 mA (2 s)
Number of drives per output: max. 2
Control cable: YY6x0.6
Input type: floating contact
Total cable length: max. 5 m
Voltage satellite inputs: approx. 5 V
Dimensions (? x H): 53 x 28 mm
Connection: screwles terminals
single wire: 1 ... 2.5 mm2
KNX supply: DC 21 ... 32 V SELV
Power consumption KNX: max. 240 mW
Connection, KNX: terminal connected to control cable
Approvals: VDE
Manufacturer: JUNG
Ref.-no.: 2531 UP
|