VR4305M4532/U - 120V dual direct ignition gas valve with standard opening - Quad Industry GmbH
Артикул: VR4305M4532/U
Наименование: 120V dual direct ignition gas valve with standard opening
Производитель: Honeywell
|
|
Overview Combination gas control for use with hot surface/direct spark systems in 120 Vac, gas-fired appliances, with capacities from 30 to 415 cfh. Features - Controls include manual valve, two automatic operators and pressure regulator.
- Compact size.
- Provides two automatic valves.
- Solenoid operated first automatic valve opens on thermostat call for heat, closes when call for heat ends.
- Diaphragm-operated second automatic valve opens under control of regulator, closes if gas or power supply is interrupted.
- Meets codes requiring dual safety shut-off.
- Natural to LP and LP to Natural conversion kits available for standard and slow opening gas valves.
- Adjustable servo regulator effectively maintains almost constant gas output pressure under wide fluctuations in gas supply pressure.
- ON/OFF lighting sequence.
Product Specifications - Application
- Single Stage
- Includes
- Two 3/4 x 1/2 in. reducer bushings, Natural to LP Conversion Kit, One 1/2' x 3/8' reducer bushing
- Item Type
- Product
- Mounting
- 0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically.
- Frequency
- 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL Component Recognized.
- Approvals, Canadian Standards Association
- 112395
- Tradeline Value
- Tradeline
- Electrical Connections
- 1/4 in. male quick-connects, 24 in. (610 mm) leadwires.
- Voltage
- 120 Vac
- Operating Temperature Range (F)
- -40 F to +175 F
- Operating Temperature Range (C)
- -40 C to +79 C
- Approvals, Canadian Gas Association
- CSA Design Certified: File No. L2025007.
- Body Pattern
- Straight-through
- Opening Characteristics
- Standard
- Pressure Ratings (psi)
- 1/2 psi
- Pressure Ratings (kPa)
- 3.5 kPa
- Inlet/Outlet Size (in.)
- 3/4 in. x 3/4 in.
- Pressure Tapping
- 1/8 in. NPT with plug
- Approvals, American Gas Association
- AGA Design Certificate: L2025007
- Type of Fuel
- Natural
- Capacity (kBtuh)
- At 1 in. wc p.d.-- 300,000 BTUh: 30,000 BTUh minimum
- Pressure Regulator Setpoint (in. wc)
- 3.5 in. wc
- Pressure Regulator Setpoint (kPa)
- 0.87 kPa
- Ignition Type
- Direct Ignition
- Anticipator Setting
- 0.13 A
| | | | |
|