7KM3133-0BA00-3AA0 - SENTRON PAC3100; LCD; 96X96MM POWER MONITORING DEVICE PANEL MOUNT TYPE FOR MEASUREMENT OF ELECTR. VALUES UC: 110-250VDC / 100-240VAC UE: MAX.480/277V; 45-65HZ IE: X/5A AC TERMINAL CONNECTION (siemens) - Quad Industry GmbH

Артикул: 7KM3133-0BA00-3AA0
Наименование: SENTRON PAC3100; LCD; 96X96MM POWER MONITORING DEVICE PANEL MOUNT TYPE FOR MEASUREMENT OF ELECTR. VALUES UC: 110-250VDC / 100-240VAC UE: MAX.480/277V; 45-65HZ IE: X/5A AC TERMINAL CONNECTION (siemens)
Производитель: Siemens


Наименование продукта
SENTRON PAC3100; LCD; 96X96MM POWER MONITORING DEVICE PANEL MOUNT TYPE FOR MEASUREMENT OF ELECTR. VALUES UC: 110-250VDC / 100-240VAC UE: MAX.480/277V; 45-65HZ IE: X/5A AC TERMINAL CONNECTION
Жизненный цикл продукта
7KM3133-0BA00-3AA0">
7KM3133-0BA00-3AA0"> Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
7KM3133-0BA00-3AA0"> 2009-09-03
Manuals weitere>>
7KM3133-0BA00-3AA0"> Справочник по аппарату SENTRON Многофункциональное измерительное устройство PAC3100   2009-11-12
Similar to image
SENTRON PAC3100; LCD; 96X96MM POWER MONITORING DEVICE PANEL MOUNT TYPE FOR MEASUREMENT OF ELECTR. VALUES UC: 110-250VDC / 100-240VAC UE: MAX.480/277V; 45-65HZ IE: X/5A AC TERMINAL CONNECTION
 
General technical data:
product designation   multimeter
product brand name   SENTRON
Product-type designation   PAC3100
Size of multimeter / company-specific   size 96
Design of the product   basic
Product function    
  • voltage measurement
  Yes
  • current measurement
  Yes
  • active power measurement
  Yes
  • reactive power measurement
  Yes
  • pulse measurement
  No
  • frequency measurement
  Yes
Item designation    
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  P
  • according to DIN EN 61346-2
  P
 
Measurement:
Measuring methode    
  • for voltage measurement
  TRMS
  • for current measurement
  TRMS
Type of measured value detection   complete
Curve form of the voltage   sinusoidal or distorted
Measurable line frequency Hz 45 65
Operating mode for measured value detection    
  • automatic line frequency detection
  Yes
  • set at 50 Hz
  No
  • set to 60 Hz
  No
 
Measuring inputs for voltage:
Measurable supply voltage    
  • between (PE)N and L / for AC / maximum nominal value
V 277
  • between the outer conductors / for AC / maximum nominal value
V 480
  • between (PE)N and L / for AC
V 11.5 332.4
  • between the outer conductors / for AC
V 20 576
Supply voltage / between the outer conductors / for AC    
  • maximum permissible
V 576
Measuring category / for voltage measurement   CATIII
Outer conductors and neutral conductors internal resistance    
  • for voltage measurement
M? 0.84
Power consumption / for voltage measurement    
  • per phase
mW 131.2
Measuring range extension for voltages    
  • with external voltage transformers
  Yes
 
Measuring inputs for current:
Measurable current    
  • 1 / for AC / nominal value
A 5
Relative measurable current / for AC % 0.2 120
Continuous current / for AC / maximum permissible A 10
Apparent power consumption / for current measurement    
  • with measuring range 5 A / per phase
mVA 500
Short-time current resistance (Icw) / limited to 1 s / rated value A 100
Zero-point suppression / for current measurement   10 mA
  • for neutral conductor current
  45 mA
Measuring category / for current measurement   CATIII
Measuring range extension for currents    
  • with external current transformers
  Yes
 
Fault limits:
Reference condition / for metering precision   according to IEC61557-12 (K55)
Formula for relative total measurement inaccuracy    
  • for measured variable voltage
  +/- 1.0 %
  • for measured variable current
  +/- 1.0 %
  • for measured variable output
  +/- 1.0 %
  • for measured variable active power
  +/- 1 %
  • for measured variable reactive power
  +/- 3 %
  • for measured variable output factor
  +/- 1 %
  • for measured variable active energy
  Class 1 according to IEC 61557-12 and IEC62053-21
  • for measured variable reactive energy
  Class 3 according to IEC61557-12 and IEC62053-23
 
Supply voltage:
Design of the power supply   power supply with a wide range of voltages
Type of voltage / of supply voltage   AC/DC
Relative symmetrical tolerance / of the supply voltage % 10
Measuring category / supply voltage   CATIII
Supply voltage / 1 / at AC V 100 240
Supply voltage frequency    
  • 1 / rated value
Hz 50
  • 2 / rated value
Hz 60
Apparent power consumption    
  • without expansion module(s) / typical
V·A 10
Supply voltage / 1 / for DC V 110 250
 
Digital input:
Number of digital inputs   2
Design of the switching input   Self-supplied
Operating conditions for digital inputs / external voltage supply   No
Input voltage / at the digital input    
  • for DC / max.
V 30
Input current / at the digital input    
  • final value for signal<0>-recognition
mA 0.5
  • initial value for signal<1>-recognition
mA 2.5
Load impedance / at the digital input    
  • initial value for signal<0> detection
?

Назад в раздел